HomeMy WebLinkAboutORD 1029ORD 1029pT3(ÌìÀl ORDINANCE NO. 1029 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF BALDWIN PARK ADDING CERTAIN PROVISIONS RELATING TO UNREINFORCED MASONRY BUILDINGS TO THE CITY'S BUILDING REGULATIONS. THE CITY COUNCIL OF THE CITY OF BALDWIN PARK DOES ORDAIN AS FOLLOWS: SECTION 1. That Chapter 15.44, entitled UNREINFORCED MASONRY BUILDING CODE"1 is hereby added to Title 15 of the Baldwin Park Municipal Code to read as follows: 15.44.010. Purpose. The purpose of this Chapter is to promote public safety and welfare by reducing the risk of death or injury to persons, and damage to property that may result from the effect of earthquake damage on unreinforced masonry bearing wall buildings constructed prior to March 20, 1933. Such buildings have been widely recognized for their susceptibility to structural earthquake damage. This Chapter shall not be deemed to require electrical, plumbing, mechanical or fire safety systems existing in buildings which are of unreinforced masonary construction, to be altered when work is required to be accomplished as to such buildings, unless such systems constitute a hazard to life or property. This Chapter provides systematic procedures and standards for identification and classification of buildings which have unreinforced masonry bearing walls, based on their present use. Priorities, time periods and standards are also established under which these buildings are required to be structurally analyzed and anchored. Where the analysis determines the existence of structural deficiencies, this Chapter requires the building to be strengthened or demolished. This Chapter also provides a method by which the City may, on an emergency basis, order the repair and/or rehabilitation of buildings and structures suffering structural damage in an earthquake. Portions of the State Historical Building Code SHBC") established under Part 8, Title 24 of the California Code of Regulations are included in this Chapter. 15.44.020. Scope. The provisions of this Chapter shall apply to all buildings in existence as of the effective date of this Chapter which have unreinforced masonry bearing walls as defined herein. BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl EXCEPTION: This Chapter shall not apply to detached one- or two-family dwellings and detached apartment houses containing fewer than five dwelling units and used solely for residential purposes. 15.44.030. Definitions. In addition to the definitions set forth in the City's Zoning and Building Regulations, and the applicable definitions in Sections 2302 and 2312 of the Uniform Building Code, the following definitions shall apply to this Chapter: BUILDING" shall mean any building or structure which has one or more unreinforced masonary bearing walls; and SUPERINTENDENT" shall mean the Superintendent of Building Inspection of the City; and ESSENTIAL BUILDING" shall mean any Building housing a hospital or other medical facility having surgery or emergency treatment areas, fire or police stations, municipal government disaster operation and communica- tion centers; and HIGH-RISK BUILDING" shall mean any Building not classified an essential building having an occupant load as determined pursuant to this Chapter of 100 occupants or more, or any building with 2 or more stories, with bearing walls within 20 ft. of a major thoroughfare. EXCEPTION: A high-risk Building shall not include the following: A. Any Building having exterior walls braced with masonry cross walls or woodframe cross walls spaced less than 40 feet apart in each story. Cross walls shall be full-story height with a minimum length of 1 1/2 times the story height; and B. Any Building used for its intended purpose, as determined by the Director, for less than 20 hours per week; and MEDIUM-RISK BUILDING" shall mean any Building not classified as a High-Risk Building or an Essential Building having an occupant load as determined by this Chapter of 20 occupants or more; and LOW-RISK BUILDING" shall mean any Building not classified an essential building having an occupant load as determined by Section 3302(a) of the Uniform Building Code of less than 20 occupants. UNREINFORCED MASONRY BEARING WALL"' shall mean a masonry wall in a Building having all of the following charac- teristics: 1. Provides the vertical support for a floor or roof; and BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl 2. The total superimposed load is over 100 pounds per linear foot; and 3. The area of reinforcing steel is less than 50 per- cent of that required by this Chapter. 15.44.040. Rating Classifications. The rating classifications set forth in Table No. 15.44-A are hereby established and each Building shall be placed in one such rating classification by the Superintendent. The total occupant load of the entire Building as determined by this Chapter shall be used to determine the rating classification. EXCEPTIONS: For the purpose of this Chapter, portions of buildings constructed to act independently when resisting seismic forces may be placed in separate rating classifications. 15.44.050. General Requirements. The owner of each Building shall cause a structural analysis to be made of the Building by a civil or structural engineer or architect licensed by the State of California, to determine whether the Building meets the minimum earth- quake standards set forth in this Chapter. If the Building does not meet the minimum earthquake standards specified in this Chapter, the owner shall cause it to be structurally altered to conform to such standards or cause the Building to be demolished. The owner of a Building shall comply with the requirements set forth above by submitting such a structural analysis to the Superintendent for review and approval within the stated time limits: a) Within 270 days after the service of an order referred to in Section 15.44.060 Order"), a structural analysis shall be prepared and submitted to the Superintendent. Such analysis, which is subject to approval by the Superintendent, shall demonstrate that the Building meets the minimum requirements of this Chapter, or if such structural analysis reflects that the Building does not meet the requirements of this Chapter; and b) Within 120 days after the Superintendent's approval of such structural analysis, the owner of the shall submit to the Superintendent for approval, plans for the proposed structural alterations of the Building necessary to comply to the minimum requirements of this Chapter; and c) Within 120 days after service of the Superintendent's approval of the structural analysis, the Building owner shall submit to the Superintendent for approval plans for the installation of wall anchors in accordance with the requirements specified in this Chapter or BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl d) Within 270 days after the service of the Order, the Building shall be made to comply with the requirements of this Chapter, and e) If the owner has not completed the work to render the Building in compliance with the provisions of this Chapter within 270 days following the service of an Order, the owner shall demolish the Building. After plans are submitted and approved by the Superintendent, the owner shall obtain the necessary building permits, and shall commence and complete the required construction within the time limits set forth in Table No. 15.44-B. These time limits shall begin to run from the date the Order is served. Owners electing to comply with Subsection C) of this Section are also required to comply with Subsection b) or d) of this section, provided, however, that the time periods provided for in such Subsections b) and d) and the time limits for obtaining a building permit, commencing construction and completing construction for complete structural alterations set forth in Table No. 15.44-B shall be extended in accordance with Table No. 15.44-C. Each such extended time limit, except the time limit for commencing construction, shall begin to run from the date the order is served in accordance with Section 15.44.060(b). The time limit for commencing construction shall commence to run from the date the Building permit is issued. 1115.44.060. Administration. a) Service of Order. The Superintendent shall issue an Order, as provided in Section 15.44.060(b), to the owner of each Building. The Superintendent shall, upon receipt of a written request from the owner, order that a Building be made to comply with this Chapter prior to the times for such Building set forth in this Chapter * b) Contents of Order. The Order shall be in writing and shall be served either personally or by certified or registered mail upon the owner as shown on the last equalized assessment, and upon the person, if any, in apparent charge or control of the Building. The Order shall specify that the Building has been determined by the Superintendent to be subject to the provisions of this Chapter and, therefore, is required to meet the minimum seismic standards of this Chapter. The Order shall specify the rating classification of the Building and shall be accompanied by a copy of this Chapter. c) Appeal From Order. The owner or person in charge or control of the Building may appeal the Superintendent's initial determination that the Building is subject to the provisions of this Chapter to the City Council. Such appeal shall be filed with the Council within 30 days from the service date of the Order. Such appeal shall be made in writing upon appropriate forms provided therefor by the Superintendent, and the grounds 4- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl thereof shall be stated clearly and concisely. No appeal shall be accepted unless it is timely filed and is accompanied by a filing fee in an amount as set by Council Resolution. d) Recordation. At the time that the Superintendent serves an Order, the Superintendent shall file with the Office of the County Recorder a certificate giving notice of the existence of such Order. The certificate shall also state that the owner thereof has been ordered to structurally analyze the Building and to structurally alter or demolish it. If the Building is either demolished, found not to be within the scope of this Chapter, or is structurally capable of resisting minimum seismic forces required by this Chapter as a result of structural alterations or an analysis, or is repaired so that it meets the requirements of this Chapter, the Superintendent shall file with the Office of the County Recorder a certificate stating that the said Order is of no further effect. e) Enforcement. If the owner or other person in charge or control of a Building fails to comply with any Order issued by the Superintendent pursuant to this Chapter within any of the time limits set forth in this Chapter, the Superintendent shall order that the Building be vacated and that the Building remain vacant until such Order has been complied with. If compliance with such Order has not been accomplished within a reasonable period of time, as set by the Superintendent, after the date the Building has been ordered vacated or such additional time as may have been granted by the Superintendent, the Superintendent shall process a proceeding pursuant to Chapter 8.08 of this Code to determine whether the Building is a public nuisance, and if it is, an order of abatement shall be issued. 15.44.070. Analysis and Design. a) General. Every Building shall be analyzed and constructed to resist minimum total lateral seismic forces assumed to act non concurrently in the direction of each of the main axes of the structure in accordance with the following equation: V ZIKCSW.......................( 1 5 4 4 1 The value of IKCS need not exceed the values set forth in Table No. 15.44-D based on the applicable rating classification of the building. b) Lateral Forces on Elements of Structures. Parts or portions of structures shall be analyzed and designed for lateral loads in accordance with the provisions of this Section of this Code but not less than the value from the following equation: Fp ICp SWp........................(15.44-2) 5- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl For the provisions of this subsection, the product of IS need not exceed the values as set forth in Table No. 15.44-E. EXCEPTION: Unreinforced masonry walls in Buildings not having a Rating Classification of I may be analyzed in accordance with Section 15.44.080. The value of Cp need not exceed the values set forth in Table No. 15.44-F. C) Anchorage and Interconnection. Anchorage and interconnection of all parts, portions and elements of the structure shall be analyzed and designed for lateral forces in accordance with Table No. F of this code and the equation Fp ICp SWp as modified by Table No. E. Minimum anchorage of masonry walls to each floor or roof shall resist a minimum force of 200 pounds per linear foot acting normal to the wall at the level of the floor or roof. d) Level of Required Repair. Alterations and repairs required to meet the provisions of this Chapter shall comply with all other applicable requirements of this Code unless specifically provided for in this Chapter. e) Required Analysis. 1. General. Except as modified herein, the analysis design relating to the structural£ alteration of a Building shall be in accordance with the analysis specified in this Chapter. 2. Continuous stress path. A complete continuous stress path from every part or portion of the Building to the ground shall be provided for the required horizontal forces. 3. Positive connections. All parts, portions or elements of the Building shall be interconnected by positive means. f) Analysis Procedure. 1. General. Stresses in materials and existing construction utilized to transfer seismic forces from the ground to parts or portions of the structure shall conform to those permitted by the code and those materials and types of construction specified in this Chapter. 2. Connections. Materials and connectors used for interconnection of parts and portions of the structure shall conform to the code. Nails may be used as part of an approved connector. 3. Unreinforced masonry walls. Except as modified herein, unreinforced masonry walls shall be analyzed as specified in this Code and to withstand all vertical loads as specified in this Code in addition to 6- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl the seismic forces required by this Chapter. The 50 percent increase in the seismic force factor for shear walls as specified in this Code may be omitted in the computation of seismic loads to existing shear walls. No allowable tension stress will be permitted in unreinforced masonry walls. Walls not capable of resisting the required design forces specified in this Chapter shall be strengthened or shall be removed and replaced. EXCEPTION: 1. Unreinforced masonry walls in Buildings not classified as a Rating Classification I pursuant to Table No. 15.44-A may be analyzed in accordance with this Section 15.44.080. 2. Unreinforced masonry walls which carry no design loads other than their own weight may be considered as veneer if they are adequately anchored to new supporting elements. g) Combination of Vertical and Seismic Forces. 1. New materials. All new materials introduced into the structure to meet the requirements of this Chapter which are subjected to combined vertical and horizontal forces shall comply with the provisions of this Title. 2. Existing materials. When stresses in existing lateral force-resisting elements are due to a combination of dead loads plus seismic loads, the allowable working stress specified in the code may be increased 100 percent. However, no increase will be permitted in the stresses allowed in this Chapter and the stresses in members due only to seismic and dead loads shall not exceed the values permitted by this Title. 3. Allowable reduction of bending stress by vertical lead. In calculating tensile fiber stress due to seismic forces required by this Chapter the maximum tensile fiber stress may be reduced by the full direct stress due to vertical dead loads. 15.44.080. Materials of Construction a) General. All materials permitted by this Code, including their appropriate allowable stresses and those exiting configurations of materials specified herein, may be utilized to meet the requirements of this Chapter. b) Existing Materials. 1. Unreinforced masonry walls. Unreinforced masonry walls analyzed in accordance with this section may provide vertical support for roof and floor construction and resistance to lateral loads. The bonding of such walls shall be as specified in this Title. 7- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl Tension stresses due to seismic forces normal to the wall may be neglected if the wall does not exceed the height- or length-to-thickness ratio and the in-plane shear stresses due to seismic loads as set forth in Table No. 15.44-G. If the wall height-thickness ratio exceeds the specified limits, the wall may be supported by vertical bracing members designed in accordance with this Chapter. The deflection of such bracing member at design loads shall not exceed one tenth of the wall thickness. EXCEPTION: The wall may be supported by flexible vertical bracing members designated in accordance with Section 15.44.070(b) if the deflection at design loads is not less than one quarter nor more than one third of the wall thickness. All vertical bracing members shall be attached to floor and roof construction for their design loads independently of required wall anchors. Horizontal spacing of vertical bracing members shall not exceed one half the unsupported height of the wall nor 10 feet. The wall height may be measured vertically to bracing elements other than a floor or roof. Spacing of the bracing elements and wall anchors shall not exceed 6 feet. Bracing elements shall be detailed to minimize the horizontal displacement of the wall by components of vertical displacements of the floor or roof, 2. Existing roof, floors, walls, footings and wood framing. Existing materials, including wood shear walls utilized in the described configuration, may be used as part of the lateral load-resisting system, provided that the stresses in these materials do not exceed the values shown in Table No. 15.44-H. c) strengthening of Existing Materials. New materials, including wood shear walls, may be utilized to strengthen portions of the existing seismic resisting system in the described configurations, provided that the stresses do not exceed the values shown in Table No. 15.44-I. d) Alternate Materials. Alternate materials, designs and methods of construction may be approved by the Superintendent. e) Minimum Acceptable Quality of Existing Unreinforced Masonry Walls. 1. General Provisions. All unreinforced masonry walls utilized to carry vertical loads and seismic forces parallel and perpendicular to the wall plane shall be tested as specified in this subsection. 8- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl  All masonry quality shall equal or exceed the minimum standards established herein or shall be removed and replaced by new materials. Alternate methods of testing may be approved by the Superintendent. The quality of mortar in all masonry walls shall be determined by performing in- place shear tests or by testing 8-inch-diameter cores. Alternative methods of testing may be approved by the department. Nothing shall prevent pointing with mortar of all the masonry wall joints before the tests are first made. Prior to any pointing, the mortar joints must be raked and cleaned to remove loose and deteriorated mortar. Mortar for pointing shall be Type S or N except masonry cements shall not be used. All preparation and mortar pointing shall be done under the continuous inspection of a registered deputy building inspector. At the conclusion of the inspection, the inspector shall submit a written report to the licensed engineer or architect responsible for the seismic analysis of the building setting forth the result of the work inspected. Such report shall be submitted to the Superintendent for approval as part of the structural analysis. All testing shall be performed in accordance with the requirements specified in this subsection by a testing agency approved by the Superintendent. An accurate record of all such tests and their location in the building shall be recorded and these results shall be submitted to the Superintendent for approval as part of the structural analysis. 2. Number and location of tests. The minimum number of tests shall be two per wall or line of wall elements resisting a common force, or one per 1500 square feet of wall surface, with a minimum of eight tests in any case. The exact test or core location shall be determined at the building site by the licensed engineer or architect responsible for the seismic analysis of the subject building. 3. In-place shear tests. The bed joints of the outer whether of the masonry shall be tested in shear by laterally displacing a single brick relative to the adjacent bricks in that wythe. the opposite head joint of the brick to be tested shall be removed and cleaned prior to testing. The minimum quality mortar in 80 percent of the shear tests shall not be less than the total of 30 psi plus the axial stress in the wall at the point of the test. The shear stress shall be based on the gross area of both bed joints and shall be that at which movement of the brick is first observed. 4. Core tests. A minimum number of mortar test specimens equal to the number of required cores shall be prepared from the cores and tested as specified herein. The mortar joint of the outer wythe of the masonry core shall be tested in shear by placing the circular core section in a compression testing machine with the mortar bed joint rotated 15 degrees from the axis of the 9- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl  applied load. The mortar joint tested in shear shall have an average ultimate stress of 20 psi based on the gross area. The average shall be obtained from the total number of cores made. If test specimens cannot be made from cores taken then the shear value shall be reported as zero. f) Testing of Shear Bolts. One fourth of all new shear bolts and dowels embedded in unreinforced masonry walls shall be tested by a registered deputy building inspector using a torque calibrated wrench to the following minimum torques: 1/2-inch-diameter bolts or dowels--40 foot-lbs. 5/8-inch diameter bolts or dowels--SO foot-lbs. 3/4-inch diameter bolts or dowels--60 foot-lbs. No bolts exceeding 3/4 inch shall be used. All nuts shall be installed over malleable iron or plate washers when bearing on wood and heavy cut washers when bearing on steel. g) Determination of Allowable Stresses for Design Methods Based on Test Results. 1. Design shear values. Design seismic in-plane shear stresses shall be substantiated by tests performed as specified in Subsections 3 and 4 of subdivision e) of this Section. Design stresses shall be related to test results obtained in accordance with Table No. l5.44-J. Intermediate values between 3 and 10 psi may be interpolated. 2. Design compression and tension values. Compression stresses for unreinforced masonry having a minimum design shear value of 3 psi shall not exceed 100 psi. Design tension values for unreinforced masonry shall not be permitted. h) Five percent of the existing rod anchors utilized as all or part of the required wall anchors shall be tested in pullout by an approved testing laboratory. The minimum number tested shall be four per floor, with two tests at walls with joists framing into the wall and two tests at walls with joists parallel to the wall. The test apparatus shall be supported on the masonry wall at a minimum distance of the wall thickness from the anchor tested. The rod anchor shall be given a preload of 300 pounds prior to establishing a datum for recording elongation. the tension test load reported shall be recorded at 1/8-inch relative movement of the anchor and the adjacent masonry surface. Results of all tests shall be reported. The report shall include the test results as related to the wall thickness and joist orientation. The allowable resistance value of the existing anchors shall be 40 percent of the average of those tested anchors having the same wall thickness and joist orientation. i} Qualification tests for devices used for wall anchorage shall be tested with the entire tension load 10- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl  carried on the enlarged head at the exterior face of the wall. Bond on the part of the device between the enlarged head and the interior wall face shall be eliminated for the qualification tests. The resistance value assigned the device shall be twenty percent of the average of the ultimate loads. 15.44.090. Information Required on plans. a) General. In addition to the seismic analysis required elsewhere by this Chapter, the licensed engineer or architect responsible for the seismic analysis of the building shall determine and record the information required by this section on the approved plans. b) Construction Details. The following requirements with appropriate construction details shall be made part of the approved plans: 1. All unreinforced masonry walls shall be anchored at the roof level by tension bolts through the wall as specified in Table No. 15.44-I, or by approved equivalent at a maximum anchor spacing of 6 feet. Anchors installed in accordance with this Title shall be accepted as conforming to this requirement. All unreinforced masonry walls shall be anchored at all floors with tension bolts through the wall or by existing rod anchors at a maximum anchor spacing of 6 feet. All existing rod anchors shall be secured to the joists to develop the required forces. The Superintendent may require testing to verify the adequacy of the embedded ends of existing rod anchors. Tests when required shall conform to Section 15.44.080. When access to the exterior face of the masonry wall is prevented by proximity of an existing building, wall anchors conforming to Items 5 and 6 in Table No. 15.44-1 may be used. Alternative devices to be sued in lieu of tension bolts for masonry wall anchorage shall be tested as specified in Section 15.44.080. 2. Diaphragm chord stresses of horizontal diaphragms shall be developed in existing materials or by addition of new materials. 3. Where trusses and beams other than rafters or joists are supported on masonry, ledges or columns shall be installed to support vertical loads of the roof or floor members. 4. Parapets and exterior wall appendages not capable of resisting the forces specified in this Chapter shall be removed, stabilized or braced to ensure that the parapets and appendages remain in their original position. 11- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl ORD 1029pT3(ÌìÀl  TABLE NO. 15.44-A RATING CLASSIFICATIONS Type of Building Classification Essential building I High-risk building II Medium-risk building III Low-risk building IV TABLE NO. 15.44-B TIME LIMITS FOR COMPLIANCE REQUIRED OBTAIN COMMENCE COMPLETE ACTION BY BUILDING CONSTRUCTION CONSTRUCTION OWNER PERMIT WITHIN WITHIN WITHIN Complete struc- One year 180 days Three years tural alterations or Building Demolition Wall anchor 180 days 270 days One year installation Times set forth in this Table shall run from the date an Order is issued pursuant to this Chapter. TABLE No. 15.44-C SERVICE PRIORITIES AND EXTENDED TIME PERIODS RATING OCCUPANT EXTENSION OF MINIMUM CLASSIFICATION LOAD TIME IF WALL TIME PERIODS ANCHORS FOR COMPLIANCE ARE INSTALLED WITH SERVICE OF ORDER I Any One year 0 Highest priority) II 100 or more One year 60 days 100 or more One year One year More than 50, One year One year but less than 100 More than 19, One year One year but less than 51 IV Less than 20 Two years One year Lowest priority) 13- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl TABLE NO. 15.44-D HORIZONTAL FORCE FACTORS BASED ON RATING CLASSIFICATION Rating Classification IKCS I 0.186 II 0.133 III & IV 0.100 14- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl TABLE 15.44-E HORIZONTAL FORCE FACTORS IS FOR PARTS OR PORTIONS OF STRUCTURES Rating Classification IS I 1.50 II 1.00 III & IV 0.75 15- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl TABLE NO. 15.44-F HORIZONTAL FORCE FACTOR Cp" FOR PARTS OR PORTIONS OF BUILDINGS OR OTHER STRUCTURES Part or Portion Direction Value of of Buildings of Force Cp Exterior bearing and non- Normal-to flat 0.20 bearing walls; interior surface bearing walls and partitions; interior non- bearing walls and partitions over 10 feet in height; masonry fences over 6 feet in height. Cantilever parapet and Normal-to-flat 1.00 other cantilever walls, surface except retaining walls. Exterior and interior Any direction 1.00 ornamentations and appendages. When connected to or a Any direction 0.20(2)(4) part of a building: towers, tanks, towers and tanks plus contents, racks over 8 feet 3 inches in height plus contents, chimneys, smokestacks and penthouses. When connected to or a Any horizontal 0.20(3) part of a building: direction rigidly mounted equipment and machinery not required for continued operation of essential occupancies. Tanks plus effective Any direction 0.12 contents resting on the ground. Floors and roofs acting In the plane 0.12(6) as diaphragms. of the diaphragm Prefabricated structural Any horizontal 0.30 elements, other than direction walls, with force applied at center of gravity of assembly. Connections for exterior Any direction 2.00 panels or elements. Notes: 1) See Section 15.44.070(b) for use of Cp. 2) When located in the upper portion of any Building with a ratio of 5 to 1 or greater, the value shall be increased by 50 percent. 16- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl3) For flexible and flexibly mounted equipment and machinery, the appropriate values for Cp shall be determined with consideration given to both the dynamic properties of the equipment and machinery and to the building or structure in which it is placed. 4) The Wp for storage racks shall be the weight of the racks plus contents. The value of Cp for racks over two storage support levels in height shall be 0.16 for the levels below the top two levels. 5) The design of the equipment and machinery and their anchorage is an integral part of the design and specification of such equipment and machinery. The structure to which the equipment or machinery is mounted shall be capable of resisting the anchorage forces. 6) Floor and roofs acting as diaphragms shall be designed for a minimum force resulting from a Cp of 12 applied to Wp unless a greater force results from the distribution of lateral forces in accordance with this Article. TABLE NO. 15.44-G ALLOWABLE VALUE OF WEIGHT-TRICKNESS RATIO OF UNREINFORCED MASONRY WALLS WITH MINIMUM QUALITY MORTAR Buildings with Crosswalls As Defined By Section 15.44.030 All Other Buildings Walls of one-story buildings 16 13 First-story wall of multi-story buildings 16 15 Walls in top story of multi-story buildings 14 9 All other walls 16 13 1/ Minimum quality mortar shall be determined by laboratory testing in accordance with Section 15.44.030. 2/ Table No. 15.44 G is not applicable to buildings of Rating Classification I. Walls of buildings within Rating Classification I shall be analyzed in accordance with Section 15.44.070. 17- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl TABLE NO. 15.44-H VALUES FOR EXISTING MATERIALS Existing Materials or configuration ration of Materials!' Allowable Values 1. HORIZONTAL DIAPHRAGMS a) Roofs with straight sheathing 100 lbs. per foot and roofing applied directly to for seismic shear. the sheathing. b) Roofs with diagonal sheathing 400 lbs. per foot and roofing applied directly to for seismic shear. the sheathing. C) Floors with straight tongue- 150 lbs. per foot and-groove sheathing. for seismic shear. d) Floor with straight sheathing 300 lbs. per foot and finished wood flooring. for seismic shear. e) Floors with diagonal sheathing 450 lbs. per foot and finished wood flooring. for seismic shear. f) Floors or roofs with straight Add 50 lbs, per sheathing and plaster applied foot to the to the joist or rafters/ allowable values for items 1(a) and 1(c). 2. SHEAR WALLS Wood stud walls with lath and 100 lbs. per foot plaster for seismic shear. 3. PLAIN CONCRETE FOOTINGS. f 1500 psi unless otherwise shown by tests. 4. DOUGLAS FIR WOOD Allowable stress same as No.1 D.F 6/ 5. REINFORCING STEEL ft 18,000 lbs, Per.square inch maximum- 6. STRUCTURAL STEEL ft 20,000 lbs. Per square inch 4/ Material must be sound and in good condition. 5/ The wood lath and plaster must be reattached to existing joists or rafters in a manner approved by the department. 6/ Stresses given may be increased for combinations of loads as specified in this Chapter. 18- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl TABLE NO. 15.44-I ALLOWABLE VALUES OF NEW MATERIALS USED IN CONJUNCTION WITH EXISTING CONSTRUCTION New Materials or Configuration of Materials Allowable Values 1. HORIZONTAL DIAPHRAGMS Plywood sheathing applied Same as specified directly over existing straight in Table No. 25-J sheathing with ends of plywood of the Uniform sheets bearing on joists or Building Code for rafters and edges of plywood block diaphragms. located on center of individual sheathing boards. 2. SHEAR WALLS a) Plywood sheathing applied Same as values directly over existing wood specified in Table studs. No value shall be given No. 25-K of the to plywood applied over existing Uniform Building plaster or wood sheathing. Code for shear walls. b) Drywall or plaster applied 75 percent of the directly over existing wood studs. values specified in Table No. 47-I. of the Uniform Building Code. c) Drywall or plaster applied 33 1/3 percent of to plywood sheathing over the values existing wood studs. Specified in Table No. 47-I of the Uniform Building Code. 3. SHEAR BOLTS Shear bolts and shear dowels 100 percent of the embedded a minimum of 8 inches values for plain into unreinforced masonry walls. masonry specified Bolt centered in a 2 1/2 inch- in Table No. 24-G. diameter hole with dry-pack or No values larger nonshrink ink grout around circumference than those given of bolt or dowel.- for 3/4 inch bolts shall be used. 4. TENSION BOLTS Tension bolts and tension dowels 1200 lbs. per bolt extending entirely through or dowel. unreinforced masonry walls secured with bearing plates on far side of wall with at 30 square inches of area. 7/ Bolts and dowels to be tested as specified in Section 15.44.080(f). 8/ Bolts and dowels to be 1/2-inch minimum in diameter. 19- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl5. WALL ANCHORS 15.44.090(b).l.1 a) Bolts extending to the 600 lbs. per bolt. exterior face of the wall with a 2 1/2 round plate under the head. Install as specified for shear bolts. Spaces not than 12 inches on centers. b) Bolts or dowels extending to 1200 lbs. per bolt the exterior face of the wall or dowel. with a 2 1/2-inch round place under the head and drill at an angle of 2212 degrees to the horizontal. Installed as specified for shear bolts. 6. INFILLED WALLS Reinforced masonry infilled Same as values openings in existing unrein- specified for forced masonry walls with unreinforced keys or dowels to match masonry walls. reinforcing. 7. REINFORCED MASONRY Masonry piers and walls Same as values reinforced per this specified in Chapter Table No. 15.44-B. 8. REINFORCED CONCRETE Concrete footings, walls and Same as values piers reinforced as specified specified in in this Chapter and designed for this Chapter. tributary loads. 9. EXISTING FOUNDATION LOADS Foundation loads for structures Calculated existing exhibiting no evidence of foundation loads due settlement. to maximum dead load plus live load may be increased 25 percent for dead load, and may be increased 50 percent for dead load plus seismic load required by this Chapter. 9/ Drilling for bolts and dowels shall be done with an electric rotary drill. Impact tolls shall not be used for drilling holes or tightening anchor and shear bolt nuts. 20- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀl TABLE J ALLOWABLE SHEAR STRESS FOR TESTED. UNREINFORCED MASONRY WALLS Seismic In-Plane 80 Percent of Test Average of Test Based Results in PSI Not Results of Cores On Less Than In Psi Gross Area 30 plus axial stress 20 3 psi 40 plus axial stress 27 4 psi 50 plus axial stress 33 5 psi 100 plus axial stress or more 67 or more 10 psi max." SECTION 2. The City Clerk shall certify to the adoption of this Ordinance and shall cause the same to be published in the manner prescribed by law. PASSED AND APPROVED this 15th day of November 1989. ATTEST: CITY CLERK 10! Allowable shear stress may be increased by addition of 10 percent of the axial stress due to the weight of the wall directly above. 21- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05 ORD 1029pT3(ÌìÀlSTATE OF CALIFORNIA COUNTY OF LOS ANGELES) SS: CITY OF BALDWIN PARK I, Linda L. Gair, City Clerk of the City of Baldwin Park, do hereby certify that the foregoing Ordinance No.1029 was regularly introduced and placed upon its first reading at a regular meeting of the City Council on November 1, 1989. That, thereafter, said Ordinance was duly approved and adopted at a regular meeting of the City Council on November 15 1989 by the following vote: AYES COUNCILMEMBERS LOWES, IZELL, MCNEILL, MAYOR KING NOES COUNCILMEMBERS NONE ABSENT COUNCILMEMBERS NONE ABSTAIN: COUNCILMEMBERS NONE 22- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05  5. All deteriorated mortar joints in unreinforced masonry walls shall be pointed with Type S or N mortar. Prior to any pointing, the wall surface must be raked and cleaned to remove loose and deteriorated mortar. All preparation and pointing shall be done under the continuous inspection of a registered deputy building inspector certified to inspect masonry or concrete. At the conclusion of the project, the inspector shall submit a written report to the Superintendent setting forth the portion of work inspected. 6. Repair details of any cracked or damaged unreinforced masonry wall required to resist forces specified in this Chapter. c) Existing Construction. The following existing construction information shall be made part of the approved plans: 1. The type and dimensions of existing walls and the size and spacing of floor and roof members. 2. The extent and type of existing wall anchorage to floors and roof. 3. The extent and type of parapet corrections which were performed in accordance with of this Code. 4. Accurately dimensioned floor plans and masonry wall elevations showing dimensioned openings, piers, wall thickness and heights. 5. The location of cracks or damaged portions of unreinforced masonry walls requiring repairs. 6. The type of interior wall surfaces and if reinstalling or anchoring of ceiling plaster is necessary. 7. The general condition of the mortar joints and if the joints need pointing. 15.44.100. Tables. The Tables attached hereto marked TABLE No. 15.44-A through TABLE No. 15.44-J," inclusive, are made a part of this Code by this reference, and shall apply as provided in this Chapter. 15.44.110. Nuisance Abatement Whenever an Order of Abatement is issued pursuant to Section 8.08 of this Code, which Order requires recon- struction or repair of a Building, the provisions of this Chapter shall apply to all work of reconstruction and repair required pursuant to such Order. 15.44.120. Effective Date of Chapter. This Chapter shall become effective on 1989. 12- BIB] 37651-U01 ORD-U02 1029-U02 LI2-U03 FO4404-U03 FO4427-U03 DO4433-U03 C5-U03 ORDINANCES-U03 10/11/2001-U04 ADMIN-U04 ORD-U05 1029-U05 NOV-U05 15-U05 1989-U05