HomeMy WebLinkAboutORD 014ORD 014ê79wU ×Pì!b ORDINANCE NO. AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF BALDWIN PARK AMENDING THE BALDWIN PARK MUNICIPAL CODE BY ADDING THERETO NEW PARTS TO BE KNOWN AS ARTICLE III, CHAPTER 1, PARTS 1, 2,3,4,5,6,7,8,9,10,11,12,13,14,15, 16 17 18 and 19. THE CITY COUNCIL OF THE CITY OF BALDWIN PARK DOES ORDAIN AS FOLLOWS: SECTION 1. Article III Public Safety, Chapter 1 Fire Prevention, of the Baldwin Park Municipal Code, is hereby amended to read as follows: ARTICLE III PUBLIC SAFETY Chapter 1 FIRE PREVENTION Part 1 ADMINISTRATION AND ENFORCEMENT. 3100.101. Title. This ordinance shall be known as the Fire Prevention Code" of the City of Baldwin Park and may be cited as such and will be referred to in the Baldwin Park Municipal Code as this Code." County Fire Warden" shall mean the Fire Warden Officer of Los Angeles County, or his duly authorized representative. County Forester Warden" shall mean the Los Angeles County Forester Warden, or his duly author- ized representative. 3100.102. Scope. The following provisions pertain to the extinguishment of fires, and the preventing, eliminating or minimizing of the fire hazard for the safety of life and property. 3100.103. Extent.. Nothing in this Code shall be con- strued as applying to the transportation of any article or thing shipped in conformity with the regulations prescribed by the Interstate Commerce Commission, nor applying to the Military, Naval or Postal forces of the United States, nor to the duly organized Militia of the State of California. This Code shall be in addition to the measures of fire prevention as set forth in the laws and regulations of the State of California and the United States except as provided above. 3100.104. Enforcement Duties. 1. It shall be the duty of the County Fire Warden to enforce the various provisions of this Code and any subsequent ordinances amending the same ORD 014ê79wU ×Pì!b and all orders and ordinances of the City Council of the City of Baldwin Park and Laws of the State of California re- lating to: a) The prevention and suppression of fires. b) The maintenance of automatic and other fire alarm and extinguishment equipment. c) Storage and use of flammable material. d) Maintenance of adequate means of egress in case of fire from factories, stores, hotels, apartment houses, asylums, hospitals, places of public assem- blage, and all other places in which a number of persons are housed, live, work, or congregate. e) Investigation of the cause, origin and circumstances of fires. 2. In connection with the enforcement of this Code, regulations of the National Fire Protection Association and of the National Board of Fire Underwriters shall be considered standard good practice requirements, and for the purpose of reference in connection with the enforcement of this Code a complete set of such current regulations shall be kept on file in the office of the Fire Prevention Bureau of the Department of County Forester and Fire Warden and City Clerk of the City of Baldwin Park. 3100.104.2. The provisions of this Code are not intended to prevent the use of materials, devices or appliances offered as an alternate for the materials, devices or appliances re- quired by this Code, if submitted to the County Fire Warden and they are in his opinion found to be the equivalent, in the particular qualities involved, of the material, device, or ap- pliance specified herein. 3100.104.3. Whenever the Forester and Fire Warden makes a finding that any material, device, or appliance offered as an alternate for materials, devices, or appliances required by this Code is equivalent, in the particular qualities involved, of the materials, devices or appliances required by this Code, he shall, within one week of making such finding, notify the City Council of the City of Baldwin Park in writing specifying: a) The type of alternate material, device or appliance. b) The material, device, or appliance for which it may be substituted. c) The reasons for his opinion. 3100.105. Power to Enforce Code. For the purpose of en- forcing this Code and other ordinances or state laws pertain- ing to the prevention of fires or protection of the City of Baldwin Park from fire, the County Fire Warden shall have the powers of a police officer. 3100.106. Power to Enter Premises. The County Fire Ward- en shall have the right to enter any building, structure, ve- hicle, car, vessel, premises or place in the City of Baldwin ORD 014ê79wU ×Pì!b Park for the purpose of making inspections or investigations which under the provisions of this Code may be deemed neces- sary, or for the purpose of enforcing the provisions of this Code or other ordinances or state laws pertaining to the pre- vention of fires and the protection of life and property from fire. Any official badge or uniform of the Los Angeles County Department of County Forester and Fire Warden or Los Angeles County Fire Protection Districts when rightfully worn shall entitle the wearer to enter and inspect as hereinbefore set forth, and it shall be unlawful for any person to interfere with, prevent, or seek to prevent the County Fire Warden from entering and examining any building, structure, vehicle, car, vessel or premises. 3100.107. Establishment of a Fire Prevention Bureau. There is hereby established in the Department of County For- ester and Fire Warden a Fire Prevention Bureau, which shall be operated under the supervision of the County Fire Warden. 3100.108. Power of County Fire Warden to Designate Yen TO Enforce Code. The County Fire Warden shall, subject to all provisions of law, detail to the Fire Prevention Bureau an assistant to be designated as Fire Prevention Engineer, and an assistant to be designated as Assistant Fire Prevention Eng- ineer, and shall detail and designate such other men as shall, from time to time, be deemed necessary to enforce this Code and to carry on all fire prevention activities in the City of Baldwin Park. 3100.109. Service of Notices. The County Fire Warden on finding any condition which is likely to cause fire, or which in the event of fire would hamper or impede the efforts of the County Fire Warden to extinguish such fire in or on any building, structure, or premises, or on finding any condi- tion which constitutes a violation of any City ordinance, County ordinance or State law relating to fire hazard, fire prevention, or fire protection, provisions of which are en- forced by said County Fire Warden, or on finding any device, appliance, apparatus, equipment, or arrangement that is likely to cause fire, may notify the person responsible for such con- dition, violation, apparatus, equipment, or arrangement to cor- rect the same and to comply with the City ordinance, County ordinance or State law relating thereto, which notice shall be given in writing, stating a definite time within which such violation shall be corrected. Failure to correct the condition within the time stated shall constitute a violation of this Code. Notice may be served by the County Fire Warden either directly to the person or by sending such notices by United States mail to such persons last known mail address. 3100.110. Destruction of Signs. It shall be unlawful for any person to mutilate, alter, or destroy any sign posted by the County Fire Warden. 3100.111. Personal Liability. In the event of a fire ORD 014ê79wU ×Pì!b resulting directly or indirectly from any omission or neglect to properly comply with any written notice of the County Fire Warden, or from the violation of this Code and amendments thereto, then any such person responsible for any such omis- sion, neglect or violation, shall be liable to the City of Baldwin Park for the payment of cost and expenses for the ser- vices of the Department in the extinguishment of such fires, the costs and expenses of this service to be collected by the County Fire Warden. 3100.112. Disposal of Moneys Collected. All moneys collected for the cost of service for fires shall be paid into and become a part of the General Fund of the City of Baldwin Park. 3100.113, Permits. 1. The County Fire Warden is hereby authorized and empowered to issue permits and certificates of approval required by this Code; and it shall be the duty of the County Fire Warden to issue such permits and certificates of approval when such issuance will not unduly endanger life or property. 2. Any permit or certificate may be refused, suspended or revoked by the County Fire Warden for proper cause, or when necessary for the public safety. 3. It shall be unlawful to violate any of the provi- sions stipulated in any permit issued by the County Fire Warden. 4. No permit issued under the provisions of this Code shall release any person from any liability, civil or criminal 5. The County Fire Warden shall not issue any permit for the installation or use of any equipment or the storage of flammable liquids in any building or structure, unless such in- stallation, use, equipment or any portion of any such building or structure in which such flammable liquids are stored, or such equipment is installed or used, is in accordance with the provisions of all existing laws and ordinances pertaining thereto. 3100.114, Notification of Completion or Occupancy, The County Department of Building shall notify the County Fire Warden upon the completion of, or the issuance of any certifi- cate of occupancy for, any building or structure the occupancy of which is specifically mentioned by the provisions of this Code, and shall state the occupancy for which such certificate was issued. Upon receipt of such notification the County Fire Warden shall be charged with the enforcement of the provisions of this Code relative to such building or structure. 3100.115. Establishment of Barriers. The Peace Officers of the City of Baldwin Park, the County of Los Angeles and the County Fire Warden are hereby authorized to place barriers a- cross any street, public place, or private property, necessary or expedient to prevent accident or interference with the law- ful efforts of the County Fire Warden at the scene of any burn- ing building, structure, or material, and such Peace Officers and County Fire Warden are hereby authorized to prevent any and ORD 014ê79wU ×Pì!b all persons from passing over or under any such barrier and from entering within the space set apart or enclosed by means of such barriers, except such persons having a pass issued by the Chief of Police of the City of Baldwin Park, the County Fire Warden or Sheriff. It shall be unlawful for any person not authorized by this section to pass over or under any such barrier or to fail, refuse, or neglect to go outside of the space so enclosed when ordered so to do by the said County Fire Warden or any Peace Officer. 3100.116. Definitions: For the purpose of this Code, the following words, terms and phrases shall be deemed to have the following meaning: 1) APPROVED: Shall mean a type, material, quality, method and workmanship satisfactory to the County Fire Warden; and he may require that type, material and quality be approved by the Underwriters' Laboratories, Incorporated. 2) COMBUSTIBLE MATERIAL: Shall mean any material with a kindling temperature of one thousand 1000) degrees Fahren- heit, or less. 3) COUNTY BUILDING ORDINANCE: Shall mean County of Los Angeles Ordinance No. 2225, N.S., entitled, An ordinance adopting a building code to regulate the construction, erec- tion, enlargement, razing, alteration, repairing, removal, maintenance, moving, use and height of buildings or structures in the unincorporated territory of the County of Los Angeles" adopted March 20, 1933, as amended. 4) COUNTY ELECTRICAL ORDINANCE: Shall mean County of Los Angeles Ordinance No. 2252, N.S., entitled, An ordinance regulating the installation, arrangement, alteration, repair, use and operation of electric wiring, connections, fixtures and other electrical appliances in buildings and other struc- tures within the unincorporated territory of the County of Los Angeles," adopted April 26, 1933, as amended. 5) COUNTY FIRE WARDEN: Shall mean the Head of the De- partment of County Forester and Fire Warden of the County of Los Angeles, his duly authorized representatives, and the em- ployees of the Fire Protection Districts within the County of Los Angeles. 6) DISTRIBUTING PLANT: Shall mean any establishment in which a system is maintained for the purpose of transfer- ring or discharging flammable liquids to any railway tank car, tank truck, tank trailer, or tank semi-trailer. 7) FILM NITROCELLULOSE: Shall mean any film which has a nitrate base. 8) FILM SAFETY: Shall mean any film which has an acetate base. 9) FLAMMABLE LIQUIDS: Shall mean any liquid that will flash at a temperature of two hundred 200) degrees Fahrenheit or less. 10) FLAMMABLE LIQUIDS-Class 1: Shall mean any flammable liquid that will flash at a temperature of one hundred 100) degrees Fahrenheit or less. 11) FLAMMABLE LIQUIDS-Class IA: Shall mean any Class 1 liquid having a vapor pressure exceeding sixteen 16) pounds per square inch absolute at a temperature of one hundred 100) ORD 014ê79wU ×Pì!b degrees Fahrenheit as determined by the Reid vapor pressure method. A.S.T.M. D-323-32T.) 12) FLAMMABLE LIQUIDS-Class 2: Shall mean any flam- mable liquid that will not flash at a temperature of less than one hundred and one 101) degrees Fahrenheit, but shall not in- clude those with a flash point in excess of two hundred 200) degrees Fahrenheit. 13) FLASH POINT: Shall mean that degree of temperature at which a liquid or substance gives off vapor in sufficient quantity to flash, or burn momentarily, on the introduction of a spark or flame. The Taglibue closed cup tester shall be used in deter- mining the flash point of all fluids or liquids, and all tests shall be made in accordance with the methods of the A.S.T.M. D-323-31T. 14) GARAGE: Shall mean any public garage, private gar- age where ten 10) or more cars are stored, automobile paint shop, washing, greasing, or polishing rack or establishment in which motor vehicles are repaired, reconditioned, or stored. 15) GROUP E OCCUPANCY: Shall mean any business or es- tablishment so classified by the County Building Ordinance. 15a) LOADING RACK: Loading rack shall mean any arrange- ment of valves, piping, or metering apparatus, including any platform attached, which is or may be used for the dispensing of petroleum or its liquid by-products into any railway tank car or any vehicle" as defined in Part 5 of this Code. 16) MOTOR VEHICLE: Shall mean any self-propelled de- vice including tractors, by which any person or property is propelled, moved or drawn, but shall not apply to devices perma- nently established in a stationary position or used in conjunc- tion with stationary tracks or rails. 17) PATIENT: Shall mean any human being in ill health, sick, injured, pregnant, suffering from or afflicted with any mental or physical disease or bodily injury who is cared for in any hospital, sanitarium, sanatorium, preventorium, rest home, asylum, or similar institution. 18) PATIENT-AMBULATORY: Shall mean a patient in that state of physical fitness which will allow him to remove him- self from buildings or structures in case of fire or disaster without detrimental effect to his health and well being. 19) PATIENT-BED: Shall mean a patient in that state of physical unfitness which will not allow him to remove himself from buildings or structures in case of fire or disaster with- out detrimental effect to his health and well being. 20) PERSON: Means any individual, firm, co-partnership, joint adventure, association, social club, fraternal organiza- tion, corporation estate, trust, business trust, receiver, syn- dicate, this and any other county, city and county, muncipal- ity, district or other political subdivision, or any other group or combination acting as a unit, and the plural as well as the singular number. 21) PLACE OF PUBLIC ASSEMBLAGE: Shall mean any build- ing, structure, tent, or seating arrangement located on any lot or parcel of ground, used for the assemblage of persons and designed to accommodate more than one hundred 100) persons. ORD 014ê79wU ×Pì!b 22) PORTABLE CONTAINERS: Shall mean any vessel or receptacle used for the storage of flammable liquids the capacity of which does not exceed fifteen 15) gallons, which is of metal, sealed, free from leaks, and painted red in color. 23) PROJECTION MACHINE: Shall mean any motion pic- ture projection machine in which nitrocellulose type film is used. 24) PROJECTIONIST: Shall mean any person operating a motion picture projection machine. 25) REFINERY: Shall mean any plant in which petrol- eum is separated by distillation on a commercial scale. 26) SAFETY CONTAINER. Shall mean any vessel or re- ceptacle designed to automatically permit the escape of un- due internal pressure without danger of rupture, which is approved for the storage of flammable liquids by the Under- writers* Laboratories, Incorporated, which bears their label of approval, and which is painted red in color when used for the storage of Class 1 flammable liquids. 27) SEATING CAPACITY: Shall mean the maximum number of persons permitted to congregate or assemble in any place of public assemblage. The method of computing such capacity shall be in conformity with that set forth for Room Capacity" in the County Building Ordinance, provided that in no case shall such capacity exceed the number arrived at by allowing one hundred 100) persons for each twenty-two 22) inches of width of each exit maintained in accordance with the provi- sions of this Code. In the event that the. provisions of this Code and the County Building Ordinance conflict as to the method of computing seating or room capacity, the provisions of the County Building Ordinance shall apply to buildings constructed or occupied in conformity therewith. 28) SERVICE STATION: Shall mean any establishment dispensing Class 1 flammable liquids to motor vehicles and which establishment renders such service to the public. 29) TANK TRUCK: Shall mean any motor vehicle used for the transportation of flammable liquids and which for such purpose is provided with a tank or tanks mounted on the frame or chassis of such vehicle. 30) TANK TRAILER: Shall mean any vehicle without mo- tive power used for the transportation of flammable liquids and which for such purpose is provided with a tank or tanks mounted thereon and which is drawn by a motor vehicle. 31) TANK SEMI-TRAILER: Shall mean any vehicle of the trailer type, having one or more axles and two or more wheels, so designed and used in conjunction with a motor vehicle that some part of its own weight and that of its own load rests upon or is carried by another vehicle, used for the trans- portation of flammable liquids and for which purpose is pro- vided with a tank or tanks mounted thereon. 3100.190. Variances. The County Fire Warden may grant a variance to any provision of this Code where there are prac- tical difficulties or unnecessary hardships in the way of car- rying out the strict letter of the ordinance, and in the grant- ing of such variance the spirit of the ordinance will be ORD 014ê79wU ×Pì!b observed, public safety secured, substantial justice done, and the public will be protected to as great an extent as if the ordinance were literally enforced. Part 2 OIL FIELDS. 3100.201. Derrick.Sprinkler System. Every wooden oil derrick of greater height than seventy-two 72) feet located within two hundred fifty 250) feet or less of any other der- rick shall be maintained with a water sprinkler system in ac- cordance with the provisions of the County Building Ordinance for new construction. All signs and boxes in connection with any such sprinkler system shall be maintained in accordance with the provisions of the County Building Ordinance for new construction. Such signs and boxes shall be maintained in such condition that colors are bright and letters legible. The County Fire Warden may test any such sprinkler sys- tem at any time. At such tests water with sufficient pressure shall be applied for a sufficient period of time to insure that the entire system is in working condition. If any defects are apparent when such tests are made they shall be immediately corrected so as to make the entire system effective. 3100.202. Outside Platform. Outside platforms on steel derricks shall be maintained in accordance with the provisions of the County Building Ordinance, as required for new construc- tion. 3100.203. Extinguishers. Fire extinguisher require- ments are provided in Part 17 of this Code. 3100.204. Derrick Signs. Every drilling or producing well, and every location for a well where material has been delivered for the erection of an oil derrick, shall have placed thereon, in a conspicuous place, a legible sign not less than twelve by twenty-four 12x24) inches, with the name of the owner, name or number of lease, and number of well printed thereon. 3100.205. Location of Derrick. It shall be unlawful for any person to locate, maintain, or operate any derrick within one hundred 100) feet of any steam boiler, or any stor- age tank or container holding flammable gas or light gravity flammable oil, where the property owned or controlled by any such person will permit a greater distance. In no case shall a derrick be located, maintained or operated within twenty- five 25) feet of any such boiler, tank or container. Where the area under ownership or control of any person locating, maintaining, or operating a derrick does not permit of the one hundred 100) feet limit distance above specified, loca- tion of such derrick shall be designated by the County Fire Warden on the property owned or controlled by such person, and proper safeguards shall be provided as may be determined by the County Fire Warden. Provided that the provisions of this Section shall not ORD 014ê79wU ×Pì! b apply to flow tanks not more than two 2) in number nor greater than five hundred 500) barrels capacity each, gas traps, or electrical dehydrators. 3100.206. Location of Boiler. It shall be unlawful for any person to locate, maintain, or operate any steam boiler within one hundred 100) feet of any derrick, or any storage tank or container holding flammable gas or light gravity flammable oil, where the property owned or controlled by any such person will permit a greater distance. In no case shall a boiler be located, maintained, or operated with- in twenty-five 25) feet of any such derrick, tank or con- tainer. Where the area under ownership or control of any person locating, maintaining, or operating a boiler does not permit of the one hundred 100) feet limit distance above specified, location of such boiler shall be designated by the County Fire Warden on the property owned or controlled by such person, and proper safeguards shall be provided as may be determined by the County Fire Warden. Provided that the provisions of this Section shall not apply to flow tanks not more than two 2) in number nor greater than five hundred 500) barrels capacity each, gas traps, or electrical dehydra- tors. If more than one steam boiler is to be hereafter main- tained, or operated for a particular use, such steam boilers must be so located as to form a battery. Every such steam boiler, or battery of boilers, except when housed or enclosed, or except when elevated to a height of twenty-four 24) inches above the surrounding terrain, shall be completely surrounded by a retaining wall of not less than twenty-four 24) inches in height, constructed of non-combustible material, and lo- cated not less than fifteen 15) feet distant from such boiler, or battery of boilers; if earth is used, such retaining wall shall be not less than eighteen 18) inches in width at the top. 3100.207. Extinguishing Line. Where required, in the judgment of the County Fire Warden, every steam boiler located within one hundred 100) feet of any oil well or oil storage tank, shall be equipped with a water or steam line of not less than one 1) inch diameter, piped from a point outside the re- taining wall where required, into the boiler fire box. Such water or steam line shall be controlled by an emergency valve to be located as designated by the County Fire Warden. Such emergency control valve shall have a metal tag not less than three inches by six inches 3x6") attached thereto, which tag shall have printed thereon EMERGENCY VALVE TO BOILERS(STEAM OR WATER)." 3100.208. Emergency Shut-off' Where required in the judgment of the County Fire Warden, every steam boiler located within one hundred 100) feet of any oil well or oil storage tank, shall be equipped with emergency quick acting valve so located, outside the retaining wall where required, as to com- pletely shut off all fuel feed lines to each and every boiler. ORD 014ê79wU ×Pì! b Such valve shall be located not more than two 2) feet from the valve controlling the steam or water line to the fire box, and shall have a metal tag not less than three inches by six inches 3x6") attached thereto, which tag shall have printed thereon EMERGENCY VALVE TO BOILERS FUEL LINE)". On all dry gas lines used for the purpose of furnishing fuel to boilers, or for the agitation of petroleum products within tanks, holders or containers, there shall be installed a positive shut-off valve at or near the point of entry to the lease, or a suitable location designated by the County Fire Warden. Such valve shall have a metal tag not less than three by six inches 3x6") attached thereto, which tag shall have printed thereon EMERGENCY VALVE-DRY GAS LINE-NAME, or NUMBER, of LEASE and NAME of OIL COMPANY." 3100.209. Waste-Oil Confined. 1. It shall be unlaw- ful for any person to place, divert or discharge into or upon, or permit, allow or assist in the placing, discharging or di- verting into or upon any highway, drainage canal or ditch, storm drain or flood control channel, any liquid containing oil or petroleum products. 2. It shall be unlawful for any person to cause or per- mit any oil, waste oil, refuse or waste matter to be or remain on the surface of the ground under, around or near any oil derrick, pump, boiler, oil storage or bleeder tank, or any combustible structure, except within an oil sump or Oil tank. 3100.210. Weeds. All land within a radius of one hun- dred 100) feet from any derrick, tank, building, machinery or equipment used in the development, production or storage of petroleum products shall at all times be kept free and clear from dry weeds or grass, rubbish or other flammable material. 3100.211. Smoking. It shall be unlawful for any person to smoke or throw, place or deposit any lighted or smouldering cigar, cigarette, ash, match, or other smouldering substance, within one hundred 100) feet of any oil well, derrick, or storage tank or oil sump containing petroleum or any of its fluid by-products. NO SMOKING" signs shall be posted, and all such signs shall have letters at least four 4) inches in height. 3100.212. Oil Sumps. It shall be unlawful for any per- son to use or cause to be used, or to maintain or cause to be maintained, any permanent sump for the purpose of storing petro- leum or its liquid by-products more than one 1) foot above the natural ground level unless such sump is constructed and main- tained in accordance with the provisions of the County Building Ordinance or the walls of such sump are of well compacted earth having a minimum horizontal width at the top of six 6) feet, and a maximum slope ratio of one 1) foot vertical to one and one-half 12) feet horizontal. Provided, however, that the level of the liquid in any sump shall not be allowed to rise above a point twelve 12) inches below the lowest top point of the enclosing walls of the sump, and such point shall ORD 014ê79wU ×Pì! bbe marked by a gauge or marker at least four 4) inches square, located at a point most accessible for gauging, and the top of such gauge shall indicate the maximum liquid level. All waste shall be piped into such sumps and no drain or outlet shall be permitted through the sumps at any point above the natural ground level. 3100.213. Sump Fires. It shall be unlawful for any person to set fire to, or to burn, or to cause any other per- son to set fire to or burn, any oil or liquid with petroleum content, in any sump hole, open pool, or reservoir, or to permit oil so situated upon premises belonging to such person to be burned, unless a permit therefor shall have been first obtained from the County Fire Warden. 3100.214. 1) Storage Tanks. The requirements for the storage of Flammable Liquids in Tanks are provided in Part 6 of this Code. Every oil storage tank, or group of tanks, shall have placed thereon, in a conspicuous place, a legible sign not less than twelve by twenty-four 12x24) inches with name of the owner, and the name or number of lease printed thereon. 2) Dehydrating Tanks. Tanks used for heat treating petroleum or products thereof, shall not be of the open type, nor shall the capacity of any such tank exceed two thousand 2,000) barrels. Tanks into which petroleum or any products thereof exceeding a temperature of one hundred thirty 130) degrees Fahrenheit is discharged or stored shall be equipped with a suitable vent stack which shall extend upward and ter- minate at a point at least thirty 30) feet above the ground; or a vent shall be tightly connected to a vapor recovery sys- tem of a type approved by the County Fire Warden; provided, also, that no pipe line connected to any system containing air under pressure shall enter into any such tank, and it shall be unlawful to cause or permit the contents of any such tank to be agitated with air at any time. 3100.215. Abandonment of Derrick. It shall be unlawful for any person to allow or permit any derrick, rigging or other oil or gas well drilling equipment or tanks for storage of flam- mable liquids, to remain upon any premises for a longer period than ninety 90) days after the abandonment of the well or the cessation of oil operations thereon; and for the purpose of this ordinance the following shall be deemed to be cessation of oil operations, to wit: 1) The failure to commence actual drilling operations on said premises within ninety 90) days after the date of the issuance of a building permit by the County Department of Build- ing for the erection of the oil or gas well derrick, unless the State Department of Natural Resources, Division of Oil and Gas, shall have ordered production to cease, or unless an operator shall have suspended drilling or production operations and the County Fire Warden shall have been so notified and a written permit from the County Fire Warden has been granted for a longer period. 2) The failure to prosecute diligently the actual ORD 014ê79wU ×Pì! ORD 014ê79wU ×Pì! b c) The number or name of the well. d) The name of the lease. e) Whether the derrick, if any, is of wood or steel construction. f) The location. 3100.221. Each applicant for an oil well permit shall pay to the County Fire Warden a fee of two dollars per well covered by the permit. 3100.222. Each oil well permit is valid only for the calendar year for which issued and is not transferable. Part 3 DISTRIBUTING PLANTS-FOR FLAMMABLE LIQUIDS. 3100.301. Definition. For the purpose of this Part, tank truck, tank trailer, or tank semi-trailer shall hereafter be referred to as vehicle." 3100.302. Distributing Plants. Except as otherwise provided, no flammable liquid, nor any liquid product of pe- troleum, shall be transferred or discharged into any railway tank car or vehicle except by means of suitable piping herein- after specified. 3100.303. Storage Installation. Regulations for the installation of surface or underground tanks for the storage of flammable liquids, butane or other liquefied petroleum gas are in Part 6 of this Code. 3100.304. Loading Rack. Every loading rack used in connection with the handling of flammable liquids shall be maintained of non-combustible material throughout, except that wooden flooring on runways and platforms may be used in connection therewith. 3100.305. Location of Loading Rack. Every such loading rack shall be kept separate from all other structures. Load- ing racks hereafter established shall be located a distance of not less than ten 10) feet from all other structures or tanks used for the storage of flammable liquids. A barricade, or other suitable arrangement, shall be maintained to prevent the loading of any vehicle at a lesser distance than ten 10) feet from any such tank or structure, and it shall be unlawful for any person to load, or permit the loading of, any vehicle + within the ten 10) feet distance provided. Unless approved venting apparatus is provided at loading rack, additional clearance around loading rack shall be main- tained as provided in Section 3100.306. 3100.306. Fence. Every such loading rack, except those used for loading or unloading of tank cars, shall be surrounded by a substantial fence of non-combustible material except that wooden supporting posts may be used), not less than five 5) ORD 014ê79wU ×Pì!b feet high, constructed in accordance with the provisions of the County Building Ordinance, with an adequate gate or gates at least five 5) feet high, and located not less than thirty 30) feet from such loading rack, or as much farther as to make it necessary for any vehicle to be completely within the fenced enclosure before it is in proper position to receive flammable liquids from such loading rack. Provided, however, that such clear space of thirty 30) feet shall not be re- quired in the event that such vehicle is vented by means of an approved manhole cover, flexible connections, and vent riser at a height not less than fifteen 15) feet above the ground level, satisfactory to the County Fire Warden. The area surrounding every such loading rack which is intended or used for driveway purposes shall be so arranged with relation to the gate or gates that a vehicle other than a railroad car can enter and leave the enclosure when travel- ing in a forward direction. The backing of any vehicle, other than a railroad car, containing Class 1 flammable liquids from any such enclosure into a public street or highway is expressly prohibited, 3100,307. Piping. Regulations for pipe and pipe fit- tings in connection with the operation of a loading rack are in Section 3100,613, 3 Underground) of this Code. Every load- ing spout at any such loading rack shall terminate in a nozzle, flexible tube, or funnel, constructed of non-sparking material, and the same shall be effectively bonded to the main riser pipe and to ground. There shall be installed on each such loading rack riser pipe, between the ground and the outlet, at least two 2) valves, one being of the lever-operated, quick-closing type, which may be readily operated from the runway or top of the vehicle being filled. It shall be unlawful for any person to tie or lock any such self-closing valve in the open position. Every such loading rack shall be provided with a vehicle grounding device acceptable to the County Fire Warden, Such grounding device shall be attached to any railway tank car or vehicle prior to removal of manhole cover and during the time when such vehicle is being filled or emptied at such loading rack, 3100.308. Electrical Equipment, All electrical equip- ment designed, installed and maintained for use in connection with the operation of a loading rack, including the structure and equipment thereof, within a horizontal radius of twenty 20) feet of such rack, shall be in accordance with the pro- visions of the County Electrical Ordinance. Where loading is accomplished by pumping with electrical apparatus, there shall be installed and maintained a remote power control within easy access of the operator, which shall meet with the approval of the County Fire Warden. 3100,309. Smoking, It shall be unlawful for any person to smoke, or for any person to permit smoking, on any premises ORD 014ê79wU ×Pì!b occupied as a distributing plant of Class 1 and Class lA flammable liquids; provided, however, that this provision shall not apply to any area of such premises at a greater distance than one hundred 100) feet from loading rack. 3100.310. Stop Motor. It shall be unlawful for any person to discharge, or for any person to permit to be dis- charged, any Class 1 and Class 1A flammable liquids into or out of any vehicle while the motor of any such vehicle is in operation, except as provided in Section 3100.520-(5) of this Code. 3100.311. Suns. Signs shall be maintained at the entrance gate, or gates, of every distributing plant, and near any loading rack, bearing the words, NO SMOKING" in letters at least four 4) inches in height; and there shall be installed at every loading rack a sign bearing the letters, STOP YOUR MOTOR" in letters at least four 4) inches in height; provided, however, that STOP YOUR MOTOR signs shall not be required at loading racks for railway tank cars. 3100.312. Fire Extins:uishment Equipment. Fire Extin- guishment equipment regulations are in Part 17 of this Code. 3100.313. Every person, firm, or corporation maintain- ing or operating on or after June 1, 1956, any distributing plant, shall first obtain a permit to do so. 3100.314. Permits for the maintenance or operation of distributing plants shall be issued on a calendar year basis and shall be good only for the calendar year for which issued. 3100.315. The fee for a permit to maintain or operate a distributing plant is five dollars per calendar year or fraction thereof. Part 4 REFINERIES. 3100.401. Refineries in which hydrocarbon liquids or substances are processed, and in which processes the flash point of the liquids or substances involved is reached, shall be maintained in accordance with the following provisions; 3100.402, Location. No permit shall be granted for the establishment of a refinery nor for any addition to any exist- ing refinery until after a survey, and investigation of haz- ardous conditions in connection therewith has been made by the County Fire Warden. In the event there are no institu- tional buildings or places of public assemblage within three hundred 300) feet of the proposed location of the distilling or condensing apparatus, and other conditions are consistent with the spirit and intent of this ordinance, the County Fire ORD 014ê79wU ×Pì!bWarden shall approve the granting of a permit for the loca- tion desired. A clear space of twenty 20) feet shall be maintained between any distilling or condensing apparatus or pressure storage tank having a capacity exceeding one thou- sand 1000) gallons hereafter established, in which flammable liquids or explosive vapors are confined under gauge pres- sures exceeding five 5) pounds per square inch, and any ad- joining property, and fifty 50) feet from any public side- walk, street or alley. No such tank, distilling or condens- ing apparatus shall be located a lesser distance than fifteen 15) feet from any building or structure other than those constructed in accordance with the provisions of the County Building Ordinance for Group E occupancy, tank or apparatus for the storage of flammable liquids not under pressure, established on any refinery premises a lesser distance than twenty 20) feet from the line of adjacent property which may be built upon, provided, however, that the distance may be decreased to ten 10) feet when the openings in any such building or structure are suitably protected. 3100.403. Storage. Except as otherwise provided in this Part, regulations for the storage of flammable liquids are in Part 6 of this Code. 3100.404. Fire Extinguishment Equipment. Fire Extin- guishment equipment regulations are in Part 17 of this Code. 3100.405. Clearance from Combustibles. It shall be unlawful for any person to cause or permit any refuse, waste matter, dry weeds or grass, rubbish, or similar waste combus- tible material to be kept on refinery premises. 3100.406. Fence. Except where a refinery is made inac- cessible to the public by a natural or other adequate barrier, a substantial fence of wire or other non-combustible material except that wooden supporting posts may be used) shall be maintained around any refinery. Such fence shall not be less than five 5) feet in height and unless a watchman or gate man is on duty at any openings therein, any and all openings in any such fence shall be arranged with gates which shall remain normally closed. Such fence shall be constructed in accordance with the provisions of the County Building Ordinance. 3100.407. No Smoking Signs. It shall be unlawful to smoke, or permit any person to smoke, within twenty-five 25) feet of any tank or container in which flammable liquids are stored. Signs bearing the words, NO-SMOKING" in letters not less than four 4) inches in height shall be conspicuously displayed on the premises of every refinery. 3100.408. Electrical Wiring. Regulations for electri- cal wiring near any storage tank, building, structure, or ap- paratus containing any flammable liquid or in which hazardous process takes place, are in the County Electrical Ordinance. ORD 014ê79wU ×Pì!bPart 5. TRANSPORTATION OF FLAMMABLE LIQUIDS OR LIQUEFIED PETROLEUM GASES. 3100.501. Definitions. Vehicle" wherever referred to in this part shall mean tank truck, tank trailer, or tank semi-trailer. Motor vehicle" wherever referred to in this part shall mean any motor vehicle equipped with permanent or portable tanks for the transportation or storage of liquefied petro- leum gases. Liquefied petroleum gases" wherever referred to in this part shall mean any gases derived from petroleum or natural gas which are in the gaseous state at normal atmospheric tem- perature and pressure, and which have a vapor pressure exceed- ing twenty-five 25) pounds per square inch gauge at one hun- dred 100) degrees Fahrenheit. 3100.502. Enforcement. It shall be unlawful for any person to operate any vehicle or motor vehicle on, along, or over any public highway, or any portion thereof, lying within the City of Baldwin Park except as herein specified. In the event of conflict between regulations contained in this Code and the Liquefied Petroleum Gases Safety Orders of the Indus- trial Accident Commission of the State of California, the regulations of the latter shall apply to any condition di- rectly affecting the safety of any employee. 3100.503. Permits. It shall be unlawful for any person to operate any vehicle or motor vehicle, or to utilize any skid tank for the purpose of transporting any liquefied petro- leum gas, without having first obtained a written permit so to do from the County Fire Warden. Each application for any such permit shall be made in writing for each such vehicle, motor vehicle, or skid tank, and shall contain the name and address of the applicant, the make, serial number and motor number of such tank truck or truck so utilized, or in the case of any such tank trailer, tank semi-trailer, trailer, or skid tank so utilized, the make, serial number, if any, and in the event there is no such serial number, the description of such tank trailer, tank semi- trailer, trailer, or skid tank as to readily identify the same together with a statement of the net capacity of each tank or container mounted on such vehicle or motor vehicle, or skid tank. It shall be the duty of the County Fire Warden, before issuing any such permit, to inspect each vehicle, motor ve- hicle, or skid tank for which such application is made, to ascertain if same complies with all of the provisions of this Code, or any other State law or City ordinance relative to fire safety. If, upon such inspection, the County Fire Warden determines that same so complies, such permit shall be issued. Any permit issued under the provisions of this Code shall be void at the expiration of the calendar year during which the same shall have been issued, and a, new permit for the ensuing year shall be obtained, as herein provided for. ORD 014ê79wU ×Pì!b In the event there is any structural change made in any skid tank or tank mounted on any vehicle or motor ve- hicle, for which any such permit shall have been issued, or any such latter tank is replaced by any other tank, such permit shall thereupon become IPSO FACTO VOID, and a new permit therefor shall be obtained as hereinabove provided. 3100.504. Revocation of Permits. Any such permit may be suspended or revoked by the County Fire Warden, if the vehicle, motor vehicle, or skid tank for which the same shall have been issued is constructed, or is being maintained, in violation of any provision of this Code, or of any other State law or City ordinance relating to fire safety, provided, however, that no such permit shall be revoked unless and un- til the permittee shall have been given a hearing before the County Fire Warden, upon not less than five 5) days* written notice thereof, which notice shall state the ground of com- plaint against such permittee and the time when and place where such hearing will be held. No such suspension or revocation shall be cancelled and such permit restored unless and until said permittee shall have made such changes, repairs, or alterations in such vehicle, motor vehicle, or skid tank as to cause the same to fully comply with all provisions of this Code, or any other State law or City ordinance relating to Fire Safety. It shall be unlawful for any person to transport, haul, carry, or convey, or to cause or permit to be trans- ported, hauled, carried or conveyed, any flammable liquids or liquefied petroleum gases on, along, or over any public highway lying within the City of Baldwin Park, in any such vehicle, motor vehicle, or tank the permit of which shall have been suspended or revoked, as herein provided for, un- less and until such suspension or revocation shall have been cancelled and such permit restored by the County Fire Warden. 3100.505. Posting of Permit. Each such permit except for skid tanks issued pursuant to the provisions of this Code shall be posted in a conspicuous place in the driver*s com- partment of the tank truck or truck for which the same shall have been issued, or in the case of a tank trailer, tank semi-trailer, or trailer, in a conspicuous place thereon. It shall be unlawful for any person to post, place or maintain or to cause or permit to be posted, placed or main- tained any such permit on any vehicle or motor vehicle other than the vehicle or motor vehicle for which such permit shall have been issued. 3100.506. Tank Construction. It shall be unlawful for any person to transport, haul, carry or convey, or to cause to be transported, hauled, carried, or conveyed in any vehicle any flammable liquids on, along or over any public highway ly- ing within the City of Baldwin Park, unless the tank or tanks thereon comply with the provisions of this section. 1. Material-Capacity and Gauze' Tanks shall be con- structed throughout of open hearth steel or blue annealed ORD 014ê79wU ×Pì!b steel, or equivalent, of a thickness and gauge in accord- ance with the provisions of the following table: TABLE No, 1 Capacity Gallons) Minimum Thickness of Material 600 Gallons or less 14 Gauge U.S. Std, 601 to 1200 Gallons 12 *, * 1201 Gallons to Unlimited 10 n *' Heads shall be bilged, or as an alternative shall be two 2) gauges heavier than above specified. A tolerance of ten 10) percent shall be allowed for individual tank capacities. Material other than that specified above may be used in thick- nesses which will give strength equivalent to that of open hearth or blue annealed steel. 2. Joints. Shell and head Joints shall be welded, riveted and welded, brazed or riveted and brazed, riveted and caulked, or made tight by some equally satisfactory process. 3. Test. Each compartment of the completed tank shall be tested and proven tight at five 5) pounds minimum pres- sure per square inch. 4. Tank Outlets. Tank outlets shall be substantially made and attached, to prevent breakage at this point, and to permit complete drainage. 5, Bulkheads. Tanks with compartments carrying Class 1 or Class IA flammable liquids or fuel supply for vehicle, and at the same time carrying Class 2 flammable liquids, shall be provided with an air space between the compartments thereof' equipped and maintained with drainage facilities. The pro- visions of this paragraph shall not apply to any vehicle in service prior to the date of enactment of this Code. 6. Tires. Vehicles shall be equipped with rubber tires. 7. Baffle Plates, 1) For the purpose of restraining the surging effect and providing adequate reinforcement to the shell, each tank having a cubic content in excess of one hun- dred and twenty 120) cubic feet shall have installed and main- tained at all times therein a sufficient number of transverse baffle plates, extending the full width of the tank, to divide the tank or tank compartments into units not to exceed one hundred and twenty 120) cubic feet. A tolerance of ten 10) percent shall be allowed in computing the one hundred and twenty 120) cubic feet volume specified in each of the afore- mentioned instances of this Section. Each such baffle plate shall be of the same material specified in Section 3100.506 1) hereof, and of a thickness not less than the thickness of the shell of the tank or tank compartment in which it is installed. Each baffle plate shall be substantially installed. No por- tion of the top or bottom of any such plate shall be at a greater vertical distance than eight 8) inches from the hori- zontal plane of the highest portion of the top, exclusive of the dome, or the lowest portion of the bottom, respectively, of the tank in which the same is installed. 2) Provided, that there may be maintained either at the top or the bottom of each such plate an opening of not ORD 014ê79wU ×Pì!bmore than twenty 20) inches in horizontal width, no por- tion of which opening shall be more than fourteen 14) inches vertical distance below or above the plane of that portion of the top or bottom, respectively, of such tank immediately above or below the middle of such opening, as the case may be. Provided, further, that the openings shall be staggered so that openings in such plates will not be directly opposite. 3) The provisions of this subsection shall not ap- ply to any vehicle in service prior to the date of enact- ment of this Code. 3100.507. Construction of Tanks for Liquefied Petro- leum Gases. 1. All provisions of this Section shall apply to liquefied petroleum gases. Tanks shall be constructed in accordance with approved methods for safety to life and property. Conformity with the American Society of Mechani- cal Engineers Unfired Pressure Vessel Code or the Amerieaa Petroleum Institute of Unfired Pressure Vessel Code shall be prima facie evidence of compliance with this Code. All tanks shall be designed with circular cross section. 2. I.C.C. Containers Exempt. Containers meeting the requirements of the Interstate Commerce Commission for trans- portation of liquefied petroleum gases via common carrier are exempt from the provisions of this section. 3. Working Pressure. Tanks on vehicles or motor ve- hicles shall be designed for a working pressure of not less than the vapor pressure of the contents at the temperatures and under the conditions hereafter specified: 1) Tanks other than fuel tanks shall in no case be designed for a working pressure of less than one hundred and twenty-five 125) pounds per square inch. 2) Fuel tanks for motor vehicles protected against solar and motor heat shall be designed for the vapor pressure of the contents at a temperature of not less than one hundred and thirty 130) degrees Fahrenheit, but for a pressure of not less than one hundred and seventy-five 175) pounds per square inch gauge. The minimum thickness of such tanks shall be not less than one-tenth 0.1) inches if made of steel. Material of equivalent strength may be accepted, provided, however, that this provision shall not apply to tanks in service at the time of the passage of this Code and which are designed for a pressure of not less than one hun- dred and fifty 150) pounds per square inch gauge when the vapor pressure of the contents does not exceed bne hundred and fifty 150) pounds per square inch gauge at one hundred and thirty 130) degrees Fahrenheit. Unprotected tanks against solar and motor heat and fuel tanks on tractors shall be designed for a vapor pressure of the contents at a temperature of not less than one hundred and forty 140) degrees Fahrenheit, and in no case for a pressure of less than one hundred and seventy-five 175) pounds per square inch gauge, provided, however, that this provision shall not apply to tanks in service at the time of the passage of this Code and which are designed for a pressure of not less than one hundred and fifty 150) pounds per square inch gauge ORD 014ê79wU ×Pì!bin the event the vapor pressure of the contents does not ex- teed one hundred and fifty 150) pounds per square inch gauge at a temperature of not less than one hundred and forty 140) degrees Fahrenheit. 4. Warning Signs. Tanks other than fuel tanks of a water capacity of more than seventy-five 75) gallons shall bear the sign, INFLAMMABLES" not less than fourteen 14) inches long, in letters not less than twelve 12) inches high. The color of letters shall be black on a white or red background. 5. Safety Devices. Safety and gauging device regula- tions are in Part 6 of this Code. 6. Tank Label. Each tank for liquefied petroleum gas shall have permanently attached to it a brass or other non- ferrous metal plate upon which shall be stamped: 1) Name of manufacturer. 2) Year built. 3) Thickness of heads and shell. 4) Manufacturer's serial number of vessel. 5) Maximum working pressure. 6) The words: THIS TANK FOR ONLY," the blank space to be filled in with the trade name or other designation of the par- ticular gas for which built. If this plate is not readily visible from the ground, a dupli- cate plate shall be placed neat the filling connection. 3100.508. Vents. 1. Pressure-Vacuum Vent. Each ve- hicle tank compartment for Class 1 and 2 flammable liquids shall be provided with a vacuum and pressure operating vent with an effective opening of forty-four one-hundredths 44) square inches minimum. Each tank compartment for Class 1A flammable liquids shall be equipped with a relief valve set to relieve at five 5) pounds gauge pressure, and such relief valve shall have a minimum area equivalent to one and one-half 12) inch diameter orifice. 2. Emergency Vent. Each tank compartment for Class 1A and 1 flammable liquids shall be provided with venting facil- ities so constructed as to provide minimum free opening of one and twenty-nine thirty-seconds 1-29/32) inches diameter for purpose. of relieving such internal pressure as may be created by exposure fires; provided, that if such venting facilities incorporate a fusible element the fusing temperature of such element shall not exceed 2000F. The provision of this subsection shall not be effective as to any vehicle in service prior to date of enactment of this Code until one year after the effective date thereof. 3. Gauge Connection. Each tank compartment for Class IA flammable liquids shall be equipped with a one-quarter J) inch nipple and valve to which may be connected a pressure gauge for the determination of pressure contained within the tank compartment. 3100.509. Dome Indicator. Each such tank, or each com- partment thereof, shall be equipped with and there shall be at all times be maintained thereon, an expansion dome having a ORD 014ê79wU ×Pì!b capacity of not less than three-quarters 3/4) of one 1) percent of the aggregate capacity of such tank or compart- ment and the dome in connection therewith. It shall be unlawful for any person to fill, or to cause or permit to be filled, any such tank or compartment beyond or above the base of such dome: Provided, however, that the provisions of this section shall not be deemed or construed to require any such dome in the event that the tank or compartment is equipped or pro- vided with an indicator permanently installed thereon accu- rately set at and indicating not less than three-quarters 3/4) of one 1) percent of the total capacity of such tank or compartment. It shall be unlawful for any person to fill, or cause or permit to be filled, any tank or compartment which has no such dome beyond the ninety-nine and one-quarter 99j) per- cent of the total capacity thereof. 3100.510. Internal Valves. Each compartment of a gravity discharge tank used for the transportation of flam- mable liquids shall be equipped with a reliable and effici- ent shut-off valve, located inside the shell of the tank in the compartment outlet, and except during unloading, dis- charging, or dumping of contents such valve shall be kept closed. The operating mechanism of such valve shall be pro- vided with a fusible link or links which will cause valve to close automatically in case of fire, and such mechanism shall also be provided with a secondary control, remote from the tank filling parts and discharge faucets for use in the event of fire or accident during delivery operations. In every case there shall be provided between the shut- off valve seat and discharge faucet a shear section which will break under strain, unless discharge piping is so ar- ranged as to afford the same protection, and leave shut-off valve seat intact. The foregoing provisions of this Section shall not be- come effective on any vehicle in service prior to the date of enactment of this Code until one 1) year after the effective date thereof. Mobile tanks of over one thousand 1000) gallons water capacity used regularly and principally for the transporta- tion of liquefied petroleum gases on public highways shall have an internal valve or an automatic excess flow valve on any liquid discharge connection, or other device or arrange- ment which will provide equivalent safety of operation. Liquid piping over one and one-half 12) inch iron pipe size for tanks used for the transportation of liquefied petro- leum gases shall preferably be of steel, and all joints welded except for the connection to the tank valve which may be a flanged or screwed connection designed for a working pressure of two hundred and fifty 250) pounds per square inch, or the test pressure of the tank, whichever is the higher, 3100,511. Valve and Faucet Connections. All draw-off valves or faucets on vehicles or motor vehicles shall have ORD 014ê79wU ×Pì!b discharge end threaded or otherwise designed to permit of tight connection with hose or piping extending to fill pipe. 3100.512. Fastenings and Supports. 1. Tanks. Each tank installed or maintained on any such vehicle or motor ve- hicle shall be securely bolted or clamped to the frame of the chassis of such vehicle or motor vehicle, and so installed as to prevent such tank from shifting or slipping thereon. Tanks other than fuel tanks, or skid tanks for the transportation of liquefied petroleum gases, permanently mounted on any motor vehicle shall be on saddles or bolsters with the center of gravity as low as possible. Skid tanks adapted to be hauled on flat truck bodies shall be provided with permanent skids attached to the tank, and with suitable means for attaching the tank firmly to the chassis during transportation. Fasten- ings of tanks to chassis shall be designed to withstand load- ings in any direction equal to the filled weight of the tank with a factor of safety of four 4). Where truck binding chains or wire ropes are used to hold down skid tanks of more than one thousand 1000) gallons water capacity, not less than three such chains or ropes distributed over the length of the tank shall be used, and the skids shall be blocked or other- wise secured against shifting on the bed or frame. Fuel tanks on motor vehicles, except tractors shall be secured in place by fastenings designed to withstand loadings in any direction equal to four 4) times the filled weight of the tank with a safety factor of four 4). Lugs, brackets, or other attach- ments intended to carry such loadings, shall not be welded, riveted or brazed to the shell or head in a manner which might result in tearing of holes in the tank. 2. Trailer Couplings and Fastenings. a) Any trailer shall be securely attached to the propelling or pulling con- veyance to prevent such trailer from becoming disconnected or detached therefrom. b) No trailer shall be coupled to or be propelled by any tank semi-trailer except that if both trailer and tank semi-trailer are equipped with automatic braking devices which, in the opinion of the County Fire Warden, will provide reasonable safety in the event that either or both such semi- trailer and trailer becomes disconnected from the truck or tractor, then such trailer may be coupled to and be propelled by such tank semi-trailer. 3100.513. Grounding. Tanks, chassis, axles, and springs on vehicles and motor vehicles shall be metallically intercon- nected, and such vehicles or motor vehicles shall be equipped with a drag chain long enough to reach the ground in order to ground such static charge as may be present. 3100.514. Leaks. Each such tank and each compartment thereof, and each valve, faucet, hose or other fixture or ap- purtenance thereto, used in connection with any vehicle or motor vehicle shall at all times be kept in good state of re- pair, clean and free from leak at any point. ORD 014ê79wU ×Pì!b 3100,515, Wiring. No artificial light of any kind except lights produc*d by electricity shall be placed or maintained on any vehicle or motor vehicle. 3100.516. Protection Against Collision. 1, Bumper. When draw-off valves or faucets project beyond frame at rear of vehicle or motor vehicle, same shall be adequately pro- tected against collision by bumper or other device. 2, Road Clearance. Fuel tanks on vehicles and motor vehicles shall be installed with as much clearance as prac- ticable, but never with less than one 1) inch more than the minimum normal road clearance of the vehicle or motor vehicle under the maximum loaded condition. This minimum clearance shall be to the bottom of the tank or to the lowest fitting on the tank, whichever is lower. All connections and fittings on fuel tanks must be adequately protected to pre- vent damage due to accidental contact with stationary objects, or from loose objects thrown up from the road. Bottom drain plugs must be of steel, 3. Side Mount Protection. Fuel tanks mounted on the side of vehicles or motor vehicles, outside the chassis or frame, shall be designed or arranged with guard, shield, or equivalent protection to minimize the hazard of mechanical injury to such tanks and piping or valves attached, 3100,517. Supply Line. 1, Control Valve. The fuel supply line of each tank truck or truck transporting lique- fied petroleum gases shall have installed therein, and at all times maintained in good working order, a shut-off valve or valve control, between the fuel tank and the carburetor of the engine thereof, which valve or valve control shall be located in a position most easily accessible for operation from the driver's compartment or the ground. 2, Carburetor Protection. On and after August 1, 1942, an efficient, reliable, and approved device shall be installed and maintained on any carburetor to provide direct drainage of overflow therefrom. 3100,518. Mufflers. The muffler and muffler pipe on each such tank truck shall be so installed and maintained as to prevent any liquid from such tank from spilling or leaking upon such muffler, or from coming in contact therewith. Hori- zontal mufflers shall be equipped with a metal shield, so con- structed, installed and maintained as to adequately cover the body of such muffler plus a minimum distance of six 6) inches both to the front and rear thereof; and there shall be pro- vided a space of not less than one 1) inch between such muf- fler shield and the muffler. 3100.519, Fire Extineuishers. Fire extinguisher re- quirements are in Part 17 of this Code. 3100.520. Filling and Discharging. It shall be unlaw- ful for any person to fill in whole or in part any vehicle with Classes 1A or 1 liquids, or any motor vehicle with lique- fied petroleum gases or to withdraw same therefrom, unless the ORD 014ê79wU ×Pì!b following is complied with: 1. During filling operation electrical contact shall be maintained between fill pipe and truck or trailer tank. This bone shall be made before removing covers of fill open- ings of any vehicle. 2. Connections. 1) During unloading operation, pro- vision shall be made for a continuous electrical bond between the vehicle or motor vehicle and the receiving container, when delivery is made through hose having a metal conductor which is separated from a grounded conductor by a non-conduct- ing substance. 2) No person shall dispense any Class 1 flammable liquid from any vehicle or motor vehicle to any underground tank or container unless the connections of any piping or hose connecting the two vessels are sufficiently tight to prevent the escape of any such liquid or any vapor therefrom during the dispensing operation. 3. No bucket or container other than one constructed entirely of metal and which shall be leak tight, shall be used for the purpose of delivering, conveying or drawing or distributing any flammable liquids of the classes named in this section. A metallic connection shall be maintained be- tween such bucket or container and draw-off valves when such flammable liquids are so withdrawn. 4. The driver or attendant of any vehicle or motor ve- hicle shall remain within ten 10) feet of such vehicle or motor vehicle or delivery hose thereof, while same is being wholly or partially filled or discharged. 5. During loading or unloading operation, the motor of any tank truck or self-propelled conveyance shall be shut off or stopped. However, in instances where the pumping of con- tents of vehicle or motor vehicle to receiving container is necessary, the provisions of this section shall not be con- strued as prohibiting the use of a power operated pump for such purposes, the power being obtained from the truck motor or other internal combustion engine. When such condition exists, the motor of the truck or other internal combustion engine shall be stopped during the period necessary for making of loading or unloading connection and stopped again before such connection is broken. 6. It shall be unlawful for any person to dispense flam- mable liquids from any vehicle or liquefied petroleum gases from any motor vehicle into any container use of which is pro- hibited, or in any manner contrary to the provisions of this Code. 7. It shall be unlawful for any person to dispense, or permit the dispensing of any liquefied petroleum gas into any tank or container for the purpose of transportation, in an amount preventing the maximum expansion of such gas at tank design temperature, or to dispense into any tank or container any such gas the vapor pressure of which is in excess of the allowable working pressure of such tank or container at the specified design temperature, provided, however, that from Oct- ober to March, inclusive, the vapor pressure may be equal to the allowable working pressure of the tank or container at a temperature of twenty 20) degrees Fahrenheit lower than the ORD 014ê79wU ×Pì!b design temperature. 3100.521. Smoking. It shall be unlawful for any per- son to smoke, or to light or strike any match or to other- wise have or produce any fire or to cause or produce any com- bustion of any kind in the open air in or upon or within a distance of ten 10) feet from any vehicle containing any Class lA or Class 1 flammable liquid or motor vehicle con- taining liquefied petroleum gases or within twenty-five 25) feet of any such vehicle when such Class lA or Class 1 flam- mable liquid is being placed into or is being discharged therefrom, or within fifty 50) feet of any motor vehicle when liquefied petroleum gas is being placed into or is be- ing discharged therefrom. 3100.522. Exposure to Opea Flames. No vehicle or motor vehicle shall enter any public garage where there is located an open flame within fifty 50) feet of any such vehicle un- less all tanks and compartments thereof are freed of all petroleum or hydrocarbon vapor. 3100.523. Parking-Leaving Vehicle or Motor Vehicle Unattended. It shall be unlawful to park and leave unattended any vehicle or motor vehicle on private property, unless such vehicle or motor vehicle is within a locked enclosure iso- lated from adjacent buildings or other precautions are taken satisfactory to the County Fire Warden. Truck, trailer, and skid tanks used for storage as well as transportation of liquefied petroleum gases shall, during the time of such storage, be assigned to permanent locations on private property, not less than fifty 50) feet from any building, provided, however, that this shall not apply to shelters referred to in Part 6 of this Code. The premises near any such vehicle, motor vehicle or tank shall be kept clear of dry grass, weeds, or other vege- tation, or waste combustible material. Part 6 STORAGE AND USE OF FLAMMABLE LIQUIDS, LIQUEFIED PETROLEUM GASES, AND COMBUSTIBLE MATERIALS 3100.601. Definitions. 1. Liquefied petroleum gases" wherever referred to in this Part shall mean any gases derived from petroleum or natural gas which are in the gaseous state at normal atmospheric temperature and pressure, and which have a vapor pressure exceeding twenty-five 25) pounds per square inch gauge at one hundred 100) degrees Fahrenheit. 2. Except as otherwise provided in this Code, it shall be unlawful for any person to store or permit to be stored, to dispense or permit to be dispensed, any flammable liquids or liquefied petroleum gases except as provided in this Part; pro- vided, however, that the provisions of this Part affecting storage shall not be deemed to apply to alcoholic beverages, ORD 014ê79wU ×Pì!b nor excepting the provisions of Sec. 3100.617 to the storage of Class 2 flammable liquids in above ground or surface stor- age tanks, constructed entirely of metal, not in excess of one thousand 1000) barrels capacity, located on the land where such liquids are to be used in conjunction with orchard or grove heating, in the event that a permit for such storage is obtained from the County Fire Warden, that such tanks are maintained free from leaks, and are located not less than thir- ty 30) feet from any line of adjacent property owned or con- trolled by a person other than the one owning or controlling such tanks, and such tanks are located a distance from build- ings or structures, other than pump houses for such liquids, as set forth in the following table: TABLE No. 1A. DISTANCE FROM BUILDINGS TANK CAPACITY AND STRUCTURES 1 to 125 barrels 30 feet 126 to 250 + 50 ti 251 to 500 75 o+ 501 to 775 100 776 to 1000 150 3. When the storage, dispensing, or piping of combus- tible materials in liquid form, having a flash point in ex- cess of 200 degrees F., constitutes an undue hazard to life or property the County Fire Warden may require compliance with any or all sections of this Part. 4. Liquefied Petroleum Gases. 1) Regulations for liquefied petroleum gases used in conjunction with cooking or domestic heating appliances are in Section 3100.1609 of this Code. 2) The following provisions shall apply to the stor- age and use of Liquefied Petroleum Gases only wherein specific reference is made to such gases, provided, however, that such provisions shall not apply to such storage in marine terminals handling petroleum products exclusively, natural gasoline plants, oil refineries, oil tank farms, and plants for the manufacturing and handling of liquefied petroleum gases, where the handling and processing of flammable liquids is a part of the normal manufacturing routine already established, nor to piping beyond a pressure reducing valve in a gas system, nor to any piping or burners for orchard heating beyond a reduc- ing valve. 3) In event of conflict between regulations contained in this Code and the Liquefied Petroleum Gases Safety Orders of the Industrial Accident Commission of the State of Cali- fornia, the regulations of the latter shall apply to any con- dition directly affecting the safety of any employee. 3100.601.2. On and after June 1, 1956, any container in which Class 1 flammable liquids are placed for retail sale shall have affixed thereon a label with the following words substantially as follows: Caution" Flammable" Do not place, ORD 014ê79wU ×Pì!b store, or use near flame, or use for domestic cleaning." The letters shall be printed in red color on contrasting back- ground. The size of the letters for use on containers less than one 1) gallon capacity shall be not less than eight 8) point type. The size of letters on labels for use on con- tainers of one 1) gallon capacity and pore shall be not less than one-quarter J) inch in height. No person shall sell any flammable liquid at retail the container of which is not so labeled. 3100.601.4. No person shall sell or offer for sale at retail any Class 1 flammable liquid for the express purpose of domestic cleaning. 3100.602. Limit of Storage Within Buildings-Permit. 1. Flammable liquids shall not be stored in excess of the quantities set forth in the following table, except when the period of such storage does not exceed thirty 30) days and permit so to do is first obtained from the County Fire Warden or storage is in accordance with the provisions of Paragraph 2 of this Section; provided, however, that flammable liquids may be stored in portable tanks or buggies constructed and maintained in accordance with the provisions of Section 3100. 604 of this Code within private garages, sheds, barns, or any Group E occupancy as defined by the County Building Ordinance; and provided, further, that not more than one such portable tank or buggy shall be stored in any private garage, barn, or shed. TABLE No. 2. WITHOUT PERMIT CLASS 1 LIQUIDS Total Quantity Gallons) Manner of Storage 1 When stored in porta- ble containers 5 When stored in safety containers. CLASS 2 LIQUIDS Total Quantity Gallons) Manner of Storage A. In excess of 1 but not exceeding 5 In dwellings, apart- ment houses, hotels and private garages, when stored in portable or safety containers. B. 5 *' 10 In occupancies other than enumerated in A" when stored in portable or safety containers. C 10 25 In occupancies other than enumerated in A" when stored in safety containers. D. 25 55 When stored in steel drums in Group E occu- pancies as defined by the Count Buildin Ordinance. ORD 014ê79wU ×Pì!b shall not be deemed or construed to prohibit the storage or dispensing of Class 2 flammable liquids in other than metal containers, in the event that no such container shall ex- ceed a capacity of one 1) gallon, and that such container bears a lable designating the contents thereof; nor as pro- hibiting the storage of flammable liquids in artisanst torches, or fuel tanks of combustion engines, or in fuel reservoirs of heating or lighting appliances when the capacity of such reser- voir does not exceed one 1) gallon. 3100.604. Portable Tanks or Buggies. l. Construction: Portable tanks or buggies shall not exceed sixty 60) gallons in capacity; and shall be constructed of iron or steel at least three-sixteenths 3/16) inch thick, with all openings at top screened by not less than thirty 30) by thirty 30) mesh non-corrodible wire, and shall be painted red. Wheels shall be equipped with rubber tires, and tanks shall be hung so as not to be liable to tip over in ordinary usage. Hose shall be not more than ten 10) feet in length and shall have a continuous metal lining with metal connections throughout. A static drag chain shall be installed on tank so as to con- tact ground or flooring. 2. Location. Portable tanks or buggies containing Class 1 liquids shall not be stored beneath the first floor or ground level of any building. Portable tanks or buggies shall not be stored or used in any room or portion of any building or structure in which the floor is of wood or other material which is a poor con- ductor of electricity unless there is provided a means of adequately grounding such portable tanks or buggies. If located within a building, portable tanks or buggies shall be placed not farther than ten 10) feet from an estab- lished means of egress. No portable tank or buggy shall be filled with any Class 1 liquid inside of any building, nor shall it remain on or near any public sidewalk, street, or alley longer than is nec- essary to complete the filling operation. 3. Extinguishers. Fire extinguisher regulations are in Part 17 of this Code. 3100.605, Abandoned Tanks-Empty Containers. The stor- age of empty tanks, and containers, previously used for the storage of Class 1 flammable liquids, unless free from explo- sive vapors, shall be as provided for the storage of Class 1 flammable liquids; provided, however, that the provisions of this Section shall not apply to portable or safety containers. Tanks and containers when emptied shall have the covers or plugs immediately replaced in openings. 3100.606. Location of Surface Storage Tanks or Con- tainers Outside Buildings. 1. Surface storage tanks or con- tainers used for the storage of flammable liquids shall be established and maintained at such distances from all build- ings, structures, or line of adjoining property which may be built upon, as hereafter specified. Capacity shall be based on the total storage capacity ORD 014ê79wU ×Pì!b 2. Storage in Group B Occupancies. a) It shall be unlawful to store flammable liquids in excess of the quanti- ties set forth in Table No. 2 in any building, structure or portion of any such building or structure,unless such build- ing, structure, or portion thereof in which such flammable liquids are stored is in accordance with the provisions of the County Building Ordinance for Group E occupancy, and stor- age is in accordance with the provisions of this Part. b) Tanks, or containers, containing in excess of five 5) gallons of Class 1 liquids or fifty 50) gallons of Class 2 liquids, shall be located below the level of any piping to which they may be connected, to prevent siphoning or gravity flow, provided, however, this provision shall not apply to any glass bowl used in conjunction with any dispens- e ing device. c) Steel drums or barrels may be used if substanti- ally placed to prevent tipping or rolling. Class 1 flammable liquids shall be drawn off by means of an approved type pump inserted through a close-fitting connection inside of head during any dispensing operation. Such drums or barrels for Class 1 flammable liquids shall be adequately grounded. d) Regulations for electrical wiring are in Part 15 of this Code. 6) The aggregate storage of flammable liquids in any building, structure, or portion thereof, shall not exceed ten thousand 10,000) gallons, provided, however, that aggregate storage limit shall not apply to any building utilized solely for storage, or to any storage in a fire resistive detached room cut off vertically and horizontally in an approved man- ner from other portions of the main building. f) Nothing in this section shall be construed as pro- hibiting the storage of flammable liquids in Group E occupan- cies in operation prior to the passage of this Code and which are not in accordance with the provisions of the County Build- ing Ordinance relative to construction of Group E buildings; provided, however, that the aggregate storage capacity in any such establishment shall not be increased beyond the amount customarily stored at the time of passage of this Code. 3100.603. Portable Containers. No flammable liquids shall be stored in or dispensed into any portable container or receptacle of fifteen 15) gallons capacity or less other than an approved or safety container. Such containers shall be constructed of galvanized steel or tin plate suitable for the purpose, with all joints locked, double seamed or riveted, and soldered or made tight by some equally satisfactory method. Containers in excess of fifteen 15) gallons capacity shall be constructed in accordance with the provisions of Section 3100. 607 of this Code, provided, however, that this section shall not apply to such liquids as may for medical purposes be stored in or dispensed into other than metal containers, in the event that no such container shall exceed a capacity of one 1) gallon, and that such container bears a label designat- ing the contents thereof, nor to conventional measuring buckets of not more than five 5) gallons capacity when used in con- junction with any vehicle; provided, further, that this section ORD 014ê79wU ×Pì!b of any tank or container or the total aggregate storage cap- acity of any containers of the portable type between which a distance is not provided as set forth for tanks in Table No. 4, provided that this shall not apply to oil fields, refineries, or distributing plants. Tanks or containers in which Class 1 flammable liquids are stored and from which liquids are dispensed at such tank or container by means of valves or gravity flow shall be lo- cated a distance twice that set forth in this Section from buildings, lines of property which may be built upon, inciner- ators and other devices employing open flame. TABLE No. 3 a) SURFACE STORAGE TANKS OR CONTAINERS IN OIL FIELDS, REFIN- ERIES AND DISTRIBUTING PLANTS Distance from all Buildings, Flammable Liquids Structures, or line of ad- Capacity) joining Property which may Barrels Gallons be built upon. 1 to 266 1 to 11,172 Not less than 8 feet 267 to 720 11,173 to 30,240 Not less than 10 feet 721 to 1,600 30,241 to 67,200 Not less than 12 feet 1,601 to 2,854 67,201 to 119,868 Not less than 15 feet j855 to 5,031 Not less than 17 feet 5,032 to 10,200 Not less than 20 feet 10,201 to 15,000 Not less than 25 feet 15,001 to 23,500 Not less than 30 feet 23,501 to 40,000 Not less than 40 feet 40,001 to 70,000 Not less than 50 feet 70,001 to 95,000 Not leas than 60 feet 95,001 to 135,000 Not less than 80 feet In excess of135,000 Not less thanl20 feet b) SURFACE STORAGE TANKS OR CONTAINERS IN CONJUNCTION WITH OCCUPANCIES OTHER THAN ENUMERATED IN a) ABOVE. Distance from all Buildings, Class 1 Liquids Structures, or line of adjoining Capacity Property which may be built upon. Gallons) 1 to 5 Not less than 5 feet 6 to 10 Not less than 10 feet 11 to 25 Not less than 15 feet 26 to 50 Not less than 30 feet 51 to 100 Not less than 35 feet 101 to 150 Not less than 40 feet In excess of 150 Unlimited Not less than 50 feet Class 2 Liquids Distance from all Buildings, Capacity Structures or line of adjoining Gallons) Property which may be built upon. 150 Not less than 5 feet 151 to 500 Not less than 20 feet In excess of 500 Unlimited Not less than 30 feet ORD 014ê79wU ×Pì! b Nothing in this section shall be deemed to prohibit the location or maintenance of any tank or container at a lesser distance than set forth above from any oil derrick or Group E occupancy building. Nothing in this section shall be deemed or construed as prohibiting the storage of flammable liquids in excess of five 5) gallons within any shelter maintained solely as a protection of such storage tank or container from the ele- ments, in which event such shelter shall not be located at a lesser distance from any other building or structure than that set forth for the location of tanks or containers in above table; and in the event that more than one tank or container is housed in such shelter the amount of distance provided shall be based upon the aggregate storage capacity of all such tanks or containers, provided, however, that this provision shall not apply to any vault or shelter of Type 1 construction in accordance with the provisions of the County Building Ordinance, No tank or container of Class 1 flammable liquids shall be located a lesser distance than thirty 30) feet from any incinerator or any other device employing an open flame; nor shall any incinerator or other open flame device be main- tained and operated a lesser distance than thirty 30) feet from any tank or container of Class 1 flammable liquids. The minimum distance between above ground storage tanks shall be in accordance with the following table: TABLE N0, 4 MINIMUM DISTANCE BETWEEN SURFACE STORAGE TANKS Applies to all classes of liquids) Distance between tanks shall be based upon the cap- acity of the larger of the two tanks between which distance is to be measured Capacity of Tank Minimum Distance Between Tanks Barrels Gallons 1 to 266 1 to 11,172 Not less than 2 feet 267 to 720 11,173 to 39,240 Not less than 3 feet 721 to 1,600 30,241 to 67,200 Not less than 4 feet 1,601 to 2,854 67,201 to 119,868 Not less than 5 feet 2,855 to 5,031 Not less than 6 feet 5,032 to 10,200 Not less than 7 feet 10,201 to 15,000 Not less than 10 feet 15,001 to 23,500 Not less than 15 feet 23,501 to 40,000 Not less than 20 feet 40,001 to 70,000 Not less than 25 feet 70,001 to 95,000 Not less than 30 feet 95,001 to 135,000 Not less than 40 feet In excess of 135,000 Not less than 60 feet 2, Surface tanks for the storage of liquefied gases shall be located outside of buildings, except shelters, not less than fifty 50) feet from the nearest adjacent building ORD 014ê79wU ×Pì!!b or group of buildings, or line of adjoining property which may be built upon or from the nearest rail of a track on a railway private right of way. No such tank shall be located where walls form a pocket in which such gases might accumu- late as the result of leakage except as provided in Section 3100.617 of this Code, nor shall such tank be located less than ten 10) feet from buildings devoted exclusively to flam- mable gas manufacture or distribution. 3. When any such tank is located where apt to be tam- pered with by unauthorized persons, it shall be surrounded by a substantial wire fence, or equivalent, and when located where it may be subjected to mechanical injury by trucks, tractors, or similar equipment, such tank shall be protected by suitable curbs, fences, or posts and railing. 3100.607. Surface Tank-Container Construction: 1. Flammable Liquids. 1) Except as otherwise speci- fically provided in this section and in Subsection 2 of Sec- tion 3100.601, tanks shall be constructed in accordance with the American Petroleum Institute's Standard No. 12 A, dated September, 1938, with Supplement No. 2, dated April, 1940; No. 12 B, dated September, 1940; No. 12C Proof), dated Janu- ary, 1941; or No. 12D Proof), dated January, 1941. 2) Provisions of this Section shall not apply to drums constructed in accordance with the regulations of the Interstate Commerce Commission. The venting provisions shall not apply to any container of one hundred and ten 110) gal- lons capacity or less, provided, however, that whenever it is essential for fire safety, vents shall be maintained on con- tainers which are permanently installed. Except in refineries, no unroofed tank shall be used. 3) For liquids of thirty-five 35) degrees Baume, or heavier, tanks may be constructed of concrete, or of concrete lining on earth, in accordance with plans approved by the County Department of Building and Safety, and such plans shall be drawn by a registered engineer. 4) Tanks shall be riveted, bolted, welded, or brazed and shall be caulked or otherwise made tight in a mechanical and workmanlike manner. The top of the tank shall be securely fastened to top ring with joints of practically equal vapor tightness of those between the rings. TABLE No. 5 THICKNESS OF MATERIAL REQUIRED FOR SURFACE STORAGE TANKS. 1. Horizontal or Vertical Tanks not over 1100 Gallons Capacity. Capacity Minimum Gallons) Thickness of Material 1 to 60 18 gauge U.S. Standard) 61 to 350 16 gauge U.S. Standard) 351 to 560 14 gauge U.S. Standard) ORD 014ê79wU ×Pì!"b 2, Horizontal Tanks Over 1100 Gallons Capacity. Tanks having a diameter of not over six 6) feet shall be made of at least three-sixteenths 3/16) inch steel. Tanks having a diameter of over six 6) feet and less than eleven and one- half 11j) feet shall be of at least one quarter J) inch steel. Tanks having a greater diameter than eleven and one- half 11D feet shall be constructed in accordance with plans which shall be submitted to the County Fire Warden for ap- proval, and such plans shall be drawn by a registered engineer. 3. Vertical Tanks Over 1100 Gallons Capacity, Exception: Welded Tanks not exceeding thirty 30) feet in diameter and sixteen 16) feet in height may be constructed of ten 10) gauge material and such tanks having a diameter not exceeding twenty-one 21) feet six 6) inches and having a height not exceeding sixteen 16) feet may be constructed of twelve 12) gauge material. 5) Before a permit shall be issued for the storage of flammable liquids in any tank, such tank shall be tested and found to be free from leaks, 6) Every above ground tank, excepting floating deck type tanks of standard construction and design which contains a vapor space which must breathe shall be provided with a vent of not less than one and one-quarter 1j) inch inside diameter, and of sufficient capacity to take care of the combined breath- ing and pumping rate; provided, however, that the minimum per- missible size of all the vents shall be determined by dividing the diameter of the supply pipe by two 2) and the quotient thereof shall be the minimum inside diameter of the vents. 7) Adequate flame arresters or palate type vacuum and pressure relief valves shall be provided in all vents on tanks containing Class 1 flammable liquids, and the free area of such flame arrester shall in no case be less than the area of the vent to which the flame arrester is attached. All such flame arresters or vents shall be maintained so as to be readily ac- cessible for inspection. 2, Liquefied Petroleum Gases. 1) All provisions of this subsection shall apply to liquefied petroleum gases. Tanks shall be constructed in accordance with approved methods for safety to life and property, Conformity with the American Soc- iety of Mechanical Engineers Unfired Pressure Vessel Code or the American Petroleum Institute Unfired Pressure Vbssel Code shall be prima facie evidence of compliance with this Code. All tanks shall be designed with circular cross section, 2) I.C.C. Containers Exempt. Containers meeting the requirements of the Interstate Commerce Commission for trans- portation of liquefied petroleum gases via common carrier are exempt from the provisions of this subsection, 3) Working Pressure. Tanks shall be designed for a working pressure of not less than the vapor pressure of the contents at the temperatures and under the conditions herein- after specified: Tanks insulated or sheltered one hundred and ten 110) degrees Fahrenheit. Tanks uninsulated or unsheltered one hundred and thirty 130) degrees Fahrenheit. ORD 014ê79wU ×Pì!#b Differential of fifteen 15) degrees Fahrenheit may be applied to uninsulated or unsheltered tanks when a coat of aluminum or white paint is satisfactorily applied and maintained. In no case shall the design working pressure of tanks be less than ninety 90) pounds per square inch. 4) Tank Label, Each tank for liquefied petroleum gas shall have permanently attached to it a brass or other nonferrous metal plate upon which shall be stamped: Name of manufacturer. Year built. Thickness of heads and shell. Nanufacturerls serial number of vessel. Maximum working pressure, The words: THIS TANK FOR ONLY," the blank space to be filled in with the trade name or other designation of the par- ticular gas for which built. If this plate is not readily visible from the ground, a duplicate plate shall be placed near the filling connection. 5) Safety Devices, a. Safety Valves-Bursting Discs. Every tank regardless of size or use shall be provided with an emergency discharge opening, vented to the open air, having a total area not less than hereafter specified. Safety valves, fusible plugs, and bursting discs may be used in making up the discharge area. At least one 1) one 1) inch pipe size, spring-loaded, or equivalent, safety valve shall be used on all tanks having a water capacity in excess of three hundred 300) gallons, and at least one 1) one-quarter J) inch pipe size spring loaded, or equivalent, safety valve shall be used on all tanks having a water capacity of three hundred 300) gallons or less, except on portable containers complying with Interstate Commerce Commission regulations. The pressure at which the safety valve is set to oper- ate shall not exceed the allowable working pressure of the tank. Bursting devices shall be designed to burst at approxi- mately one hundred and fifty 150) percent of the working pres- sure; fusible plugs shall melt at approximately two hundred 200) degrees Fahrenheit. Where fusible plugs are required on tanks longer than thirty-six 36) inches at least one shall be at each end of the tank. Bursting devices and fusible plugs shall be placed in the top of the tank in order that they will discharge vapor when operating. The combined discharge cap- acity of the safety valves, fusible plugs, and bursting de- vices shall he not less than that determined by one of the fol- lowing methods: a) The quantity of gas to be released may be computed as one hundred 100) pounds per hour for each foot of surface area of the tank. The discharge capacity of safety valves may be based on the manufacturers rating for air in cubic feet per minute at sixty-eight 68) degrees Fahrenheit at the allowable working pressure multiplied by seven and six-tenths T.6) to give pounds per hour of gas mixture discharged. ORD 014ê79wU ×Pì!$b b) The total free discharge shall be not less than that computed by the formula: a 0.77A P When a free discharge area, square inch p working pressure of the tank Lbs. per square inch absolute gauge pres- sure plus 15 lbs., per square inch.) A total outside area of tank, square feet. The free discharge area of a safety valve is equal to the inside circumference of the seat multiplied by the lift at the discharge pres- sure, but it is not more than the smallest clear area of the nozzle or the inlet pipe. If the storage tank is filled by a positive displace- ment pump the safety valve liquid capacity shall be large enough to discharge the entire capacity of the pump at not over ten 10) percent above the working pressure of the tank. Safety valves shall be adjusted and tested by the sup- plier and shall be arranged with a seal or lock so that the adjustment cannot be tampered with. The popping pressure shall be indicated on an attached metal tag. Such valves shall be ordered specially ground and tested for liquefied petroleum gas service. When any tank is permanently located a distance of two hundred 200) feet from any other tank used for the storage of petroleum or combustible material, the area of pressure relief may be reduced to not less than twenty-five 25) percent of that otherwise required, provided, however, that this provi- sion shall not apply to pump houses constructed in accordance with the provisions of the County Building Ordinance for Group E occupancy. In industrial plants, discharge from safety relief valves or bursting discs shall extend upward therefrom in a vertical direction and shall be piped to a point at least ten 10) feet above the tank, but in any event such discharge shall not be less than one hundred 100) feet distant from any open flame or process likely to cause an explosion of liberated gases, provided, however, that this provision shall not apply to any discharge point piped ten 10) feet above the roof of any building or structure in which such flame or process is located. Discharge pipes for safety valves and bursting discs shall be fitted with loose rain caps of light metal. Return bends and pipe fittings shall not be installed on the upper end of the safety valve. In lieu of the rain cap the discharge pipe from a safety valve may be provided with a one-quarter k") inch drain opening in the elbow at the base of the verti- cal pipe or that provided in the body of the relief valve. b. Pressure Gauge. Each tank shall be provided with a suitable pressure gauge, adequately supported and protected. Gauge shall have a range of twice the allowable working pres- sure of such tank, and shall be equipped with a wrench nut on ORD 014ê79wU ×Pì!%b the connection nipple. A bar stock nipple drilled with one- eighth 1/8) inch diameter hole may be employed between the tank and the gauge shutoff valve in lieu of the aforementioned connection nipple. c. Liquid Level Gauge. Tanks shall be provided with a dip pipe equipped with a valve so arranged as to indicate when the liquid level reaches the maximum permitted. A metal tag or plate shall be attached, bearing the words, STOP FILLING WHEN LIQUID APPEARS." Gauge connections shall be protected against mechanical injury. Glass gauges shall be equipped with full automatic valves having ball checks in the body, metallic hand wheels equipped with knobs or holes, and high pressure gauge glass. Such a gauge shall be guarded against mechanical injury. Gauge glasses on portable or mobile tanks shall be entirely enclosed with a steel cover not less than number ten 10) gauge in thickness, and on transportation tanks shall be so located that they will not be unduly exposed to breakage in case of accident to the truck or trailer trans- porting such tank. 6) Shelter. Tank shelter construction regulations are in the County Building Ordinance. Shelters shall be arranged to completely shade any tank between the hours of ten 10) A.M., and two 2) P.M., daily during the summer months. 3100.607J. Emergency Relief of Excessive Internal Pres- sure. 1. No form of emergency relief construction shall be required on vertical tanks with cone roofs having a slope of less than two and one-half 2J) inches in twelve 12) inches where the strength of the joint between the roof and the shell is less than of the weakest vertical joint in the shell. 2. Except as provided in 1. of this section, tanks shall have some form of relief for preventing the development of excessive internal pressure in case of exposure fire sur- rounding them. This may take the form of either a weak seam in the top or at the joint between the top and the shell of the tank, or some other form of emergency relief construction. 3. In tanks where entire dependence for relief is placed upon some form of emergency relief construction other than a weak seam, it shall have a capacity comparable to that provided by such weak seam. Openings for emergency relief shall be in accordance with the following table; ORD 014ê79wU ×Pì!&b TABLE No. 6. EMERGENCY RELIEF OF EXCESSIVE INTERNAL PRESSURES IN SURFACE STORAGE TANKS Minimum Approximate diameter of free circular Emergency opening unobstructed by valve discs, Relief etc.) required to discharge petroleum Capacity vapors at the given rates for the fol- Required lowing allowable internal pressures: Capacity Cubic feet 3 Inches 1 Pound 9 Pounds 25 Pounds of per of per per per Tank Hour Water Sg. Inch Sg. Inch So. Inch 1,000 16,000 4'- 2-1/2-1 1-1/2" 1" 4,000 44,000 6-3/411 3-3/411 2-1/411 1-3/411 18,000 88,000 9-1/2" 5-1/2" 3-1/4" 2-1/21' 25,000 106,000 10-1/4" 611 3-1/2" 2-3/4-' 56,000 160,000 12-3/4" 7-1/411 4-1/4" 3-1/4" 100,000 230,000 15-1/411 8-3/4" 591 4" 155,000 290,000 17-1/411 9-3/4" 5-3/411 4-1/2" 22Z,000 330,000 18-1/411 10-1/211 61' 4-3/411 475,000 395,000 20" 11-1/411 6-3/411 5" 735,000 410,000 20-1/2" 11-1/2" 6-3/4" 5-1/4" to Unlimited 3100.608. Underground Storage Tanks. Except as other- wise provided, storage of flammable liquids shall be in under- ground tanks. No such tank or group of tanks hereafter in- stalled shall be maintained or used which has been established or installed in violation of any provision of this Part. Underground storage tanks shall be of new material, and no used or secondhand tanks shall be utilized except as provided in Section 3100.611. Underground tanks shall not be covered with earth or otherwise hidden from view until the County Fire Warden has been notified and given not less than forty-eight 48) hours in which to inspect such tanks and piping atta-ahed, and ap- proval has been received from him for such installation. 3100.609. Location. 1. Flammable liquids: Tanks bur- ied underground shall have the top of the tank not less than four 4) feet below the surface of the ground and below the lowest point in any building within a radius of thirty 30) feet, or in lieu of four 4) feet depth the tank shall be bur- ied beneath not less than eight 8) inches of earth, and four 4) inches of re-inforced concrete extending at least one 1) foot beyond the outline of the tank in all directions. Storage tanks shall be located outside the foundation walls of any building or structure, provided that tanks may be installed within the foundation walls of any building or struc- ture when such building or structure occupies all available space on the lot or parcel on which such building or structure is erected. Tanks within buildings or structures shall be buried at least one 1) foot below the floor level, and below ORD 014ê79wU ×Pì!'b the lowest point within the building or the lowest point in adjacent building within a distance of thirty 30) feet, be- neath not less than eight 8) inches of earth, and four 4) inches of reinforced concrete which shall extend at least one 1) foot beyond the outline of the tank in all directions. When necessary to prevent floating, tanks shall be se- curely anchored or weighted. Tanks or groups of tanks may be installed a lesser dis- tance than thirty 30) feet from the lowest point in any adja- cent building provided the aggregate capacity of such tank or group of tanks is not greater than set forth in Table No. 7. 2. Liquefied Petroleum Gases. Tanks for the storage of liquefied petroleum gases underground shall be buried not less than four 4) feet below the surface of the ground, and at least twenty-five 25) feet from any building or structure, or adjoining property line which may be built upon, or from the nearest rail of a track on a railway private right of way. Tanks may be located not less than ten 10) feet from build- ings devoted exclusively to gas manufacturing operations or distribution operations through piping systems. Steel saddles welded to the tanks and projecting beyond the protective coat- ing shall be provided to properly support such tanks. If ground conditions are such that the tanks may float, they shall be properly weighted. Earth shall be firmly tamped around and under such tanks. Regulations for the provision of concrete or masonry pads for tanks are in the County Building Ordinance. 3100.610. Storage Limit of Underground Tanks. 1. Open) 2. Except as otherwise provided, tanks for underground storage of liquefied petroleum gases shall not exceed fifteen thousand 15,000) gallons water capacity. 3. The capacity of any underground tank for flammable liquids shall not exceed the limit set forth in the following table, which is based on the distance between any tank and the lowest part of any adjacent building. TABLE No. 7. MAXIMUM CAPACITY OF TANKS FOR UNDERGROUND STORAGE. If top of tank is above lowest floor, basement, cellar, or part of any building which is: ess than 10 feet away 550 Gallons 11 feet to 15 feet away 1,000 16 feet to 20 feet away 2,000 21 feet to 25 feet away 3,000 26 feet to 30 feet away 5,000 31 feet to 35 feet away 7,500 36 feet to 40 feet away 10,000 41 feet to 45 feet away 20,000 46 feet to 50 feet away 50,000 More than 50 feet away Unlimited ORD 014ê79wU ×Pì!(b 3100.611. Construction of Underground Tanks: 1. Flam- mable Liquids. Tanks shall be constructed of open hearth steel, wrought iron, or equivalent, of a thickness not less than that specified in the following table: TABLE No. 8 THICKNESS OF MATERIAL REQUIRED FOR UNDERGROUND STORAGE TANKS Galvanized Iron Minimum Thickness Capacity U. S. Standard of Material Gallons Gauge Iron or Steel 1 to 1,100 12 3/16 in. 1,101 to 2,500 10 3/16 in. e 2,501 to 4,000 7 3/16 in. 4,001 to 12,000 1/4 in. 12,001 to 20,000 5/16 in. 20,001 to 30,000 3/8 in. 30,001 to 40,000 7/16 in. 40,001 to 50,000 1/2 in. For the purpose of construction, a tolerance of ten 10) percent in capacity shall be permitted for tanks of 1100 gallons and more capacity. All joints shall be riveted and caulked, brazed, welded, or made tight by some equally satisfactory process, and con- structed in a workmanlike manner. Shells of tanks shall be properly reinforced where connections are made, and all con- nections shall be made through the top of the tank above the liquid level. Tanks shall bear the Underwriterst Laboratores, Inc., label of approval and the name plate of the manufacturer, in- dicating the gauge or thickness of the metal used in such tanks, Provided, however, that tanks without the Underwriters* label of approval, or used tanks, may be installed when the County Fire Warden has ascertained that such tanks are not unduly pitted or rusted and such tanks have been subjected to a hydrostatic or pressure test of five 5) pounds per square inch witnessed by and satisfactory to the County Fire Warden or a certificate or written report of such satisfactory test as above set forth, made by a tank manufacturer, dealer, or installation contractor, has been furnished the County Fire Warden. Provided, further, that if after inspection the County Fire Warden has reasonable cause to doubt the correctness of any such certificate or written report, or that any such tanks will withstand a test as set forth above, said County Fire Warden shall, before giving approval for use, witness such test. Provided, further, that when any such tank is relocated on the same premises such test, or certificate or written re- port of such test, may be waived by the County Fire Warden. Tanks shall be protected with a coating of tar, asphaltum, or other suitable rust resisting material. At least one 1) foot of well-tamped earth or concrete shall separate each storage tank. ORD 014ê79wU ×Pì!)b No used tank shall be installed or coated with tar, asphaltum, or similar material prior to installation until the County Fire Warden shall have found it to be in satis- factory condition. 2. Liquefied Petroleum Gases. 1) All provisions of this subsection shall apply to liquefied petroleum gases. Tanks shall be constructed in accordance with approved methods for safety to life and property. Conformity with the Amert- van Society of Mechanical Engineers Unfired pressure Vessel Code shall be prima facie evidence of compliance with this Code. All tanks shall be designed with circular cross sec- tion. 2) I.C.C. Containers Exempt. Containers meeting the requirements of the Interstate Commerce Commission for trans- portation of liquefied petroleum gases via common carrier are exempt from the provisions of this subsection. 3) Working Pressure. Tanks shall be designed for a working pressure of not less than the vapor pressure of the contents at the temperatures and under the conditions here- after specified: Underground tanks ninety 90) degrees Fahrenheit. An increase in thickness of metal, for both shell and heads, shall be provided as a corrosion allowance on all bur- ied tanks. This increase in thickness shall beone-sixteenth 1/16) inch when tank is protected as provided in a. of this subsection, and one-eighth 1/8) inch when protected as pro- vided in b. of this subsection, provided, however, that in no case shall the design working pressure be less than seventy- five 75) pounds per square inch. Whenever asphalt or asphaltic materials are specified, their equivalent in protective material may be substituted in lieu thereof. a. Coating with asphaltic paint, followed by not less than three-quarters 3/4) inch thickness of asphaltic mastic applied hot and protected with a fabric covering. b. Coating with asphaltic paint, followed by a coating of asphalt at least one-eighth 1/8) inch thick applied hot over which a cover of one 1) inch mesh number twenty 20) gauge galvanized wire netting shall be applied, spaced three- eighth 3/8) inch out from the surface, covered with cement mortar applied by impact, sealed against dampness by the appli- cation of a one-eighth 1/8) inch hot asphaltic cover coat. 3100.612. Pressure Systems: 1. No system for dispens- ing flammable liquids under pressure shall be installed or maintained in or in connection with any building, except as provided in Paragraph 2 of this Section, or in refineries, distributing plants, or other establishments where the manu- facturing process requires such a system. Provided, however, that wherever such a system is permitted all piping shall be arranged to reduce the hazard of discharge within the building in the event of derangement of any such system. 2. Pressure auxiliary tanks may be used in conjunction with service stations for forcing flammable liquids into the body of pumps or dispensing devices when such tanks do not ORD 014ê79wU ×Pì!*b not less than five 5) feet from any door or other building opening; provided, however, that when fill pipe supplies tank located beneath any building or structure which occu- pies all available space on the lot or parcel on which such building or structure is erected, the County Fire Warden may permit such fill pipe to be located less than the distance specified. When located where accessible to motor vehicles, it shall terminate in a non-combustible box or casing to pre- vent mechanical injury. 6) In the event that a visible pump is connected to more than one storage tank or pressure auxiliary tank, a mani- fold shall be provided at the pump location, and a series of valves provided in the manifold so that only one tank may be drawn from at one time; and the drain or overflow from the glass bowl of such visible pump shall return to the tank from which supply is drawn. 7) Return or overflow lines from visible pumps shall be of a size and proper pitch to permit emptying glass con- tainers of such visible pumps within a time limit of thirty 30) seconds. 8) No auxiliary pressure tank shall be connected to more than one visible pump. 9) Tanks shall not be inter-connected in any manner to allow fluid to flow from one tank to another, except the pressure auxiliary tanks already provided for. 4. Vents for Underground Tanks. 1) All underground tanks, except pressure auxiliary tanks, shall be vented to the open air by means of a pipe the size of which shall be not less than required by the following table: TABLE No. 9 Fill pipe 5 in. diameter or less 1i in. diameter vent. Fill pipe 6 in. diameter 12 in. diameter vent. 2) Provided that when offsets are installed in any vent pipe riser above the ground level the size of the vent pipe shall be one-quarter k) inch larger in diameter than re- quired in Table No. 9. 3) In the event that the size or condition of any vent pipe connected to any underground tank is such as to cause flow of vapor from the fill pipe opening during filling operations, changes in the vent pipe shall be made to properly correct such condition. 4) A battery of tanks may be vented into one 1) main riser provided vents are connected together not less than eight 8) feet above the ground and that portion of the vent pipe above the point of interconnection shall be equal to the combined area of all vent pipes. 5) All vent pipes shall run without sag or trap with a free drain from the topmost point of the vent. A fall of not less than one-quarter J) inch to the foot shall be maintained toward the tank. Vents shall be installed outside of any build- ing, except that they may be embedded in walls of masonry. 6) The top of any vent shall be not less than twelve 12) feet above the ground; provided, however, that if there ORD 014ê79wU ×Pì!+b is any building located within fifteen 15) feet of such vent pipe, each such vent pipe shall extend not less than eighteen 18) inches above any fire wall, roof, or other obstruction of said building that is located within fifteen 15) feet of said vent pipe; and further provided that in no case shall the vent pipe be required to extend a greater distance than fifteen 15) feet above the ground level, but in all cases the installation shall be made so that the va- pors issuing from such vent shall not constitute a fire hazard. 7) All vent pipes shall be equipped with an ap- proved double ell or hooded fitting, the opening in which shall be not less than equal to the area of the vent pipe. 8) Auxiliary tank exhausts from visible type pumps shall be vented the same as for storage tanks; provided, than one-half 2) inch and may be connected to the vent riser of any storage tank eighteen 18) inches above the ground level. Not more than two 2) such exhaust pipes from such visible pumps shall be manifolded or connected to any stor- age tank vent riser unless the size of the pipe used for such connection and vent riser is equal to the combined area of all such pipes. 5. Piping for Liquefied Petroleum Gases. All piping, one 1) inch pipe size and over, shall be at least standard, full weight, wrought iron or steel pipe from the tank valve to any regulating or reducing valve or valve controlling any distributing main. Piping less than one 1) inch pipe size may be of seamless brass, copper, or steel tubing or standard full weight wrought iron or steel pipe. All buried iron or steel piping shall be galvanized or otherwise protected. Bur- ied pipe shall be protected from corrosion at the points where the coating or galvanizing is removed, as at threaded or welded joints, by suitable asphaltic, or other coatings. Con- nections applied to tank shells shall not be smaller than one- quarter J) inch iron pipe size, and shall be of extra strong pipe weight. Joints on iron or steel pipe shall be of welded con- struction. All fittings shall be of cast or forged steel, ex- cept that for two 2) inch pipe size or less they may be of extra heavy brass or extra heavy malleable iron. All bush- ings shall be of steel. Cast iron fittings shall not be used. Piping shall be run as directly as possible without sags or traps. Provisions shall be made for expansion, con- traction, jarring and vibration. Particular care shall be taken that connections to the storage tank are so arranged that excessive strain will not be put upon them by any settling of the foundations, or disturbances of the piping. Piping shall be rigidly braced to the tank or be otherwise constructed so that any breakage that may be possible will occur outside the valve that is next to the tank. Piping outside of buildings buried or above ground shall be fully protected against mechanical injury. If screwed fittings are used for piping, a gasoline and water insoluble compound shall be used for making up the ORD 014ê79wU ×Pì!,b joints. After installation, all piping, including the filling connections and all discharge connections up to any pressure reducing valve that may be used for the purpose of reducing pressure on the discharge, shall be tested and proved to be tight at a pressure not less than working pressure prescribed for the storage container. Valves and connections, including the nearest shutoff valve or cock, to any tank, shall have a rated steam working pressure of two hundred and fifty 250) pounds per square inch, or at least equal to the pressure of the tank as other- wise specified, whichever is the higher. Valves and connec- tions away from the tank, up to any reducing valve, shall have a rated steam working pressure of two hundred and fifty 250) pounds per square inch. All valves shall be specifically ground and packed for liquefied petroleum gas service. Cocks shall have handles permanently attached. All valves for use on tanks or as part of any lique- fied petroleum gas system or equipment shall have their ade- quacy and suitability established, through the submission and approval of certified data on materials, design and construc- tion, together with such trials, tests and demonstrations as may be essential. Cast iron valves shall not be used. All connections to tanks except special connections leading to relief valves, to bursting discs, or to fusible plugs, shall have shut-off valves at the tanks, or as close thereto as possible. If any liquid line has another valve in it away from the tank, a small liquid relief valve shall be installed between the two valves in the line to prevent exces- sive pressures being built up by expansion of the liquid in the line when both valves are shut off, except that where one of the valves is an internal tank valve, no liquid relief valve shall be required. On tanks of one thousand 1000) gallons water capacity or larger, shut-off valves may be installed between the tank and the relief valves or bursting discs, provided that the fol- lowing requirements are met: 1) Two relief valves or bursting discs are provided, each having a relieving capacity at least equal to the mini- mum requirements for the device. 2) The two shut-off valves for the relief valves or bursting discs are mechanically interlocked so that one may not be closed without the other being in the open position, or the two relief valves or bursting discs are connected to the branches of a three way, two port cock or valve of such de- sign that both ports cannot be closed simultaneously. 3) A lock is provided on the interlocked valves or on the three-way cock or valve to prevent tampering by unauthor- ized persons. Filling or discharge pipe terminal shall be outside of a building and at least fifty 50) feet from any,door or window. For underground tanks, the fillingterminal shall be so designed as to make access difficult by unauthorized per- sons. ORD 014ê79wU ×Pì!-b Storage tanks, tanks used for transportation, and fuel tanks on equipment where discharge is by gravity shall be provided with a filling connection and a vapor equaliz- ing connection to permit equalization of pressures between the two vessels between which liquid is being transferred. The same pipe may be used for filling and for discharge of liquid. 3100.614. Pumps-Dispensing Devices. 1. No pump or dispensing device shall be used in conjunction with flammable liquids, the design or construction of which can be.shown to be unsafe by the County Fire Warden. 2. Pumps or dispensing devices used in connection with any system conveying flammable liquids shall not be installed nor altered unless a permit shall first have been obtained from the County Fire Warden. No pump, dispensing valve, or dispensing device shall be used in connection with any surface storage tank for the purpose of dispensing flammable liquids or any liquid product of petroleum directly to any motor vehicle. 4. Dispensing valves shall not be connected to surface storage tanks of greater capacity than two hundred and fifty 250) gallons. 5. Dispensing valves on surface storage tanks shall be substantially locked in a closed position at all times ex- cept during dispensing operation. 6. Suitable guards shall be maintained on visible type pumps to protect glass bowls from breakage. 7. No visible type pump or visible type dispensing device shall be installed inside the walls of any building or beneath any canopy or roof covering of any building or struc- ture which is not open to the air on three 3) sides. 8. Provided, however, where it is necessary to comply with the tolerances and specifications applying to liquid measuring devices required by the State of California a visible device of not more than one 1) quart capacity may be installed, provided such device is suitably guarded against breakage. 9. No pump or dispensing device for Class 1 flammable liquids shall be located inside or in connection with any building or portion thereof, unless such building or portion thereof is constructed in accordance with regulations of the County Building Ordinance for Group E occupancies, and in which the wiring is in accordance with the provisions of Part 15 of this Code, and in which building or portion thereof no open flame or spark emitting devices are employed. 10. No pump or dispensing device for Class 1 flammable liquids hereafter installed shall be located nearer than ten 10) feet from any building, or structure, except buildings or structures used solely by Group E occupancies, or six 6) feet from the line of adjacent property which may be built upon; provided, however, that where the installation of such pump or dispensing device greatly increases the hazard to ad- jacent structures or public safety the County Fire Warden shall require such pump or dispensing device to be located at a ORD 014ê79wU ×Pì!.b greater distance; and it shall be unlawful for any person to install any such pump or dispensing device at any loca- tion providing less clearance than that designated by the County Fire Warden. Provided, further, that nothing in this paragraph shall prohibit the installation of any pump or dis- pensing device of Class 1 flammable liquids at a lesser dis- tance from any building wall of masonry or steel in which there are no openings within fifteen 15) feet of such pump or dispensing device. 11. A suitable barrier or barricade shall be main- tained to prevent the parking of any vehicle in the clear area between the required distance locations of any such dis- pensing device and any such building or line, provided, how- ever, that this shall not apply to essential, definitely i ing to or from any building opening. 12. No pump or dispensing device for Class 1 flam- mable liquids hereafter installed shall be located nearer than ten 10) feet from any public sidewalk, street, or alley. Service stations shall be maintained so that the fill opening on any vehicle into which Class 1 flammable liquids may be dispensed shall be not less than three 3) feet from any pub- lic sidewalk, street, or alley. 13. No person shall maintain any pump or dispensing device used in conjunction with Class 1 flammable liquids within distances set forth in Table No. 9A, from any elec- trical wiring light, lamp, fixture, outlet, or switch, unless such electrical wiring or electrical equipment is approved for use in explosive atmospheres and is installed in accord- ance with the provisions of the County Electrical Ordinance. TABLE No. 9A Within a horizontal radius 6 feet or less above the of hose length ground or floor level Within radius of 4 feet More than 6 feet above the ground or floor level Provided, however, that nothing in this section shall apply to any such pump or dispensing device when electrical wiring, light, lamp, fixture, outlet, or switch is installed or maintained above the roof or ceiling of any building or structure, nor when isolated by partitions or walls. 14. Pumps or dispensing devices of Class 1 flammable liquids shall be located on private property, so that any motor vehicle, the tank of which is being filled will also be on private property. 15. Pumps or dispensing devices shall be maintained free from leaks of either fluid or vapors; and in the event that same become defective or unsafe, they shall immediately be made safe or used shall be discontinued. 16. Hose used in connection with any pump or dispensing device shall be continuously electrically bonded throughout its length, and such hose shall be, at all times, free from leaks. ORD 014ê79wU ×Pì!/bExcept when used in conjunction with airplanes and service stations, such hose shall not exceed ten 10) feet in length. 3100.615. Dispensing. 1. No person shall dispense any Class 1 flammable liquid from any tank truck, tank trailer, or tank semi-trailer to any underground tank or container un- less the connections of any piping or hose connecting the two vessels are sufficiently tight to prevent the escape of any such liquid or any vapor therefrom during the dispensing op- eration. 2. No person shall dispense any Class 1 flammable liq- uids into the tank of any motor vehicle while the motor of such motor vehicle is running. 3. No person shall dispense, or permit the dispensing of any liquefied petroleum gas into any tank or container for the purpose of transportation in an amount preventing the maxi- mum expansion of such gas at tank design temperature, or to dispense into any tank or container any such gas the vapor pressure of which is in excess of the allowable working pres- sure of such tank or container at the specified design temper- ature, provided, however, that from October to March, inclu- sive, the vapor pressure may be equal to the allowable working pressure of the tank or container at a temperature of twenty 20) degrees Fahrenheit lower than the design temperature. 4. All connections made for the transfer of liquefied petroleum gases shall be in the open air or within a struc- ture open on at least three 3) sides. 3100.616. Foundations. Regulations for foundations other than of earth or wooden cushions are in the County Build- ing Ordinance. All tanks shall be electrically grounded by resting directly on moist earth, or otherwise electrically grounded to permanent moisture. 3100.617. Dikes. 1. It shall be unlawful for any per- son to use or cause to be used, or to maintain or cause to be maintained, any surface storage tank or container located out- side of any building and in which flammable liquids, petroleum or its liquid by-products or liquefied petroleum gases are, or may be, placed or stored unless such surface storage tank or container is surrounded by a natural earthen barrier, earth, masonry, or reinforced concrete walls or dikes so designed, constructed and maintained as to confine the total capacity of the largest tank or container within the same and ten 10)per- cent of the capacity of such other tanks and containers as are located within the same. Such walls or dikes shall be in- creased for each additional tank or container of smaller cap- acity located within the same by ten 10) percent of the cap- acity of such additional tank or container. Provided, however, that such natural barrier, walls, or dikes shall not be re- quired for tanks of less than two thousand 2000) gallons capacity, tanks in isolated locations, tanks located in ab- sorption plants, tanks containing Class 2 flammable liquids ORD 014ê79wU ×Pì!0bused in conjunction with orchard heating, or tanks contain- ing liquefied petroleum gases, except where in the opinion of the County Fire Warden a hazardous condition exists. 2. Any surface storage tank or container located in- side of any building and in which flammable liquids are, or may be, placed or stored shall be surrounded by masonry or reinforced concrete walls or dikes so designed, constructed, and maintained as to confine the total capacity of all such tanks or containers within the same. 3. Regulationsfor masonry and concrete dikes are in the County Building Ordinance. Dikes shall be continuous, with no openings. for piping or roadway. Earthen dikes shall have a minimum height of two 2) feet, shall be firmly and compactly built of earth from which vegetable matter and rubbish have been removed, and shall have a flat section at the top of not lees than eighteen 18) inches, and the sides shall have a slope consistent with the angle of repose of the materials of which they are constructed. A distance of not less than five 5) feet shall be maintained between any tank and any part of any dike. All walls or dikes shall be maintained to prevent any seepage, leakage, or overflow into or upon any public thoroughfare or waterway, or upon any ad- joining private or public property. 3100.618. Clearance from Combustibles. It shall be unlawful to cause or permit any oil, waste oil, refuse, waste matter, dry weeds or grass, rubbish or other flammable waste material to be or remain on or near any tank. Premises near any tank or container for the storage of liquefied petroleum gases shall be kept clear of dry grass and weeds, or other vegetation, or waste combustible material. 3100.619. Warning Signs. 1. No Smoking-Stop Your Motor. It shall be unlawful to smoke within a distance of twenty 20) feet of any pump or dispensing device used in con- junction with Class 1 flammable liquids. It shall be unlawful to cause or permit the motor of any motor vehicle to run while any Class 1 liquid is being dispensed into the fuel tank of any such motor vehicle. Wherever Class 1 flammable liquids are dispensed, a sign, or signs, bearing the words, NO SMOKING", in letters not less than four 4) inches in height, shall be conspicu- ously displayed. Wherever Class 1 flammable liquids are dispensed into the fuel tank of any motor vehicle a sign, or signs, bearing the words, NO SMOKING" STOP YOUR MOTOR", in letters not less than four 4) inches in height, shall be conspicuously dis- played. 2. Liquefied Petroleum Gases. Surface tanks for the storage of liquefied petroleum gases of a water capacity greater than seventy-five 75) gallons shall be marked on at least two 2) sides and one 1) end with a sign, INFLAMMABLES", not less than twelve 12) inches high nor less than fourteen 14) inches long, in black letters on a white or red background. ORD 014ê79wU ×Pì!1bSuch tanks permanently located shall also have the sign, NO SMOKING OR OPEN FLAME PERMITTED WITHIN FIFTY FEET." 3100.620. Seals. To prevent the use of defective or hazardous equipment or the use of equipment in violation of this Code, the County Fire Warden shall cause a seal to be placed on such equipment which is installed or in use to make it inoperative, and it shall be unlawful for any per- son totreak or permit to be broken any such seal. 3100.621. Fire Extingulshment Equipment. Fire ex- tinguishment equipment regulations are in Part 17 of this Code. 3100.622. Concrete Cisterns-Orchard Heatina. The provisions of this Part shall not apply to underground con- crete tanks or cisterns for the storage of flammable liquids used in connection with orchard or grove heating, when such tanks or cisterns are located in or near such orchard or grove and a distance of not less than eighteen 18) feet from any building, except buildings constructed in accordance with the provisions of the County Building Ordinance. Part 7 GARAGES 3100.701. Rubbish. No rubbish, waste oil, or other flammable or combustible waste material shall be allowed to accumulate or be stored in any manner that would cause or ac- cellerate fire; provided, however, that nothing in this para- graph shall be deemed to prohibit the storage of combustible waste materials when stored in metal containers with tight fitting lids, nor the storage of waste oils in accordance with the provisions of Part 6 of this Code. Oily or greasy rags or waste shall not be permitted to remain in any portion of any building or structure used as a garage except when stored in metal containers with tight fit- ting lids. 3100.702. Flammable Liquids. Flammable liquids shall not remain in any open container longer than necessary to com- plete washing operation of motor vehicle parts. Class l flam- mable liquids shall not be used for the removal of grease or oil on flooring or walls. Regulations for storage and use of flammable liquids are in Part 6 of this Code. 3100.703. Sawdust. Sawdust or other combustible mate- rial shall not be used for the purpose of absorbing flammable liquids, oils or greases in any building or structure, unless they are immediately removed upon completion of the sweeping operation. Such sweepings, unless immediately removed from the premises, shall be stored in metal containers with tight fit- ting lids. ORD 014ê79wU ×Pì!2b 3100.704. Pits: No open flame, unprotected elec- tric light, lamp, switch, or other spark emitting device shall be operated in any pit, unless such pit is free from flammable or explosive vapors. 3100.705. Fire Extinguisher Equipment: Fire ex- tinguisher regulations are in Part 17 of this Code. 3100.706. Electrical Wiring: Electrical wiring regulations are in Part 15 of this Code. 3100.707. Garage Basement: It shall be unlawful for any person to repair or clean any part or parts of any motor vehicle with flammable liquids or to dispense any Class 1 flammable liquids in any basement beneath any garage. Part 8 PLACES OF PUBLIC ASSEMBLAGE 3100.801. Classification: Places of public assem- blage shall be classified as follows: Group A Division 1: Shall include theatres having a stage on which combustible stage scenery or properties are used or employed. Division 2: Shall include motion picture theatres having a seating capacity of one thousand 1000) or more. Division 3; Shall include all auditoriums and other places of public assemblage having a seat- ing capacity in any one room of more than thirty- five hundred 3,500). Group B Division 1: Shall include motion picture theatres having a seating capacity of less than one thou- sand 1,000). Division 2: Shall include all auditoriums and all other places of public assemblage having a seat- ing capacity in any one room of five hundred 500) or more but less than thirty-five hundred 3,500). Group C Shall include all auditoriums and all other places of public assemblage having a seating capacity in any one room of one hundred 100) or more but less than five hundred 500). Group J Division 3: Shall include stadiums, reviewing stands, and amusement park structures. 3100.802. Places of Public Assemblage: No Group A, B, or C place of public assemblage which is newly constructed shall be opened to the public, nor shall any Group A or B place of public assemblage which has been closed for a longer period than thirty 30) days be reopened to the public, unless an in- spection is made by the County Fire Warden and fire extinguish- ment appliances and equipment required by Part 17 of this Code ORD 014ê79wU ×Pì!3bare found to be provided and in good working order. 3100.803. Overcrowding; It shall be unlawful to per- mit overcrowding or admittance of any person, or persons, by- yond the seating capacity of any place of public assemblage. The County Fire Warden, upon finding any overcrowded condition; or obstruction in aisles, passageways, or other means of egress; or upon finding any condition which consti- tutes a serious men4ce to life, shall cause the performance, presentation, exhibition, spectacle or entertainment to be stopped until such condition or obstruction is corrected. 3100.804. Seating Arrangement-Aisles-Means of Egress: Regulations for seating arrangements, aisles, and means of egress in places of public assemblage are in the County Build- ing Ordinance; provided, however, that seats in Group C places of public assemblage may be movable in the event that such seats are securely fastened together in groups of not less than six 6); and provided, further, that when seats in any row consist of less than six 6), or more than six 6) but less than twelve 12), the fractional number shall be securely fastened together. It shall be unlawful in any place of public assemblage while open to the public for any person to obstruct or permit any obstruction, whether permanent or movable, of any exit, foyer, aisle, passageway, or corridor, which shall include persons, floor registers, radiators, chairs, stools, stands, slot machines, easels, and similar obstructions. It shall be unlawful to obstruct, lock, or in any other way impair; or permit to be obstructed, locked, or in any other way impaired; the operation of any entrance or exit door or gate from any place of public assemblage while occupied; and such doors and gates, as well as any self-releasing hard- ware installed thereon, shall be maintained to open freely. Regulations requiring the maintenance of panic bolt type hardware on exit doors are in the County Building Ordi- nance. All entrances, exit doors, and gates shall be maintained so as not to decrease the required width of any opening, pas- sageway, or corridor in any manner whatsoever. No false door, window, or mirror shall be maintained in any place of public assemblage as to give the appearance of a doorway, exit or passageway. No rope shall be: placed across the opening between any aisle and any row of seats unless approved safety fastener is used thereon, which will release the rope when pressed against. Exit light fixtures shall be maintained with green let- ters or background and shall be illuminated during the time any place of public assemblage is open to the public when there is insufficient natural light to read in occupied portions. Programs for stage presentations in places of public assemblage shall contain a notice, in heavy type not less than one-eighth 1/8) inch in height, consisting of the following words: FIRE NOTICE Look around now, choose the nearest exit ORD 014ê79wU ×Pì!4b to your seat, and in case of disturbance of any kind, to avoid the dangers of panic, WALK do not run) to that exit." 3100.805. Proscenium Curtain: Proscenium asbestos curtain in Groups A and B places of public assemblage shall be raised and lowered at least once before any performance; and shall remain in the lowered position except during the time of such performance, or when raised to perform necessary work. It shall be unlawful to place or permit to be placed any excess weight on the counterweight of any curtain, or in any other way to interfere with or render inoperative auto- matic lowering feature. Such curtain shall be maintained to effect the lowered position from a fully raised position in less than thirty 30) seconds, but the last five 5) feet of travel shall be effected in not less than five 5) seconds. Such curtain shall be maintained free from tears, peep- holes, or other openings. 3100.806. Proscenium Doors: Doors in proscenium walls shall be maintained in a completely closed position when such doors are not being actually used for the purpose of permit- ting ingress or egress. 3100.807. Curtain Motors: No electric motor shall be maintained near any curtain or drape on any stage unless a suitable guard is installed around such motor, maintaining a clearance of not less than two 2) feet. 3100.808. Stage Ventilation: Stage ventilation regu- lations for places of public assemblage are in the County Building Ordinance. Stage ventilators shall be operated to an open and closed position prior to any performance, or not less than once each day during which any Performance is given. 3100.809. Firemen: Whenever in the opinion of the County Fire Warden it is essential for public safety in any place of public assemblage; due to the number of persons or the nature of the performance, exhibition, display, or con- test; it shall be the duty of the owner, agent, or lessee to employthe number of competent, experienced firemen required and approved by such County Fire Warden. Such firemen shall report at least once a week to the County Fire Warden, and be subject to his orders at all times; shall be on duty in uni- form at such places of public assemblage during the whole time it is open to the public; shall, before every performance, ex- amine all fire apparatus required by this Code and see that the same is in proper place and in good working order; shall keep diligent watch during every performance for fires and take prompt measures for extinguishing any fires that may oc- cur; and shall not be required or permitted while on duty as such firemen to act as scene shifter or stage hand, or to do any other work or perform any duties or service other than as herein specified. ORD 014ê79wU ×Pì!5b 3100.810. Dressing Rooms: No shelving or cupboard shall be maintained in any dressing room, property room, or other storage room unless of non-combustible material. No wall lighting fixture shall be maintained in any dressing room unless protected by suitable guard. No container for disposal of waste shall be maintained in any dressing room, unless such container is of metal and equipped with a self-closing lid. 3100.811.-l. Smoking: It shall be unlawful for any person to smoke or permit the smoking of any cigar, cigarette, pipe, or tobacco in any form whatever in any place of public assemblage when open to the public. Provided, however, that nothing in this section shall be deemed to prohibit such smok- ing in any reviewing stand; on any stage when such smoking is a part of the play or production; in the retiring rooms, smok- ing rooms, mezzanine floor, balconies, in Group A, Divisions 1 and 2, and Group B, Division 1, places of public assemblage, of Type 1, or fire resistive construction, as defined in the County Building Ordinance; in the retiring rooms, smoking rooms, or such other places as may be designated for that pur- pose by the County Fire Warden in Group A, Division 3; Group B, Division 2, and Group C places of public assemblage. Provided, further, however, that smoking shall be per- mitted in such designated places other than on stages in Group A and B places of public assemblage only in the event that floor coverings, furniture, and drapes therein are of fire resistive material or have been given an adequate fire retard- ant treatment. 2. Open Flame. It shall be unlawful for any person to cause or permit any open flame to be used in any place of public assemblage, except when used in conjunction with ap- proved heating appliances, unless the County Fire Warden shall have first approved such use and caused written permit to be issued therefor. 3100.812. Metal Containers: It shall be unlawful to store or permit to be stored, any oily or greasy rags or mops except when kept in approved metal containers with tight-fitting lids. Metal containers shall be maintained in all rooms where paper towels are provided. There shall be provided in any projection booth, en- closure, or room in which nitro-cellulose type film is used, a metal container with a tight-fitting lid for the disposal of scrap film; and it shall be unlawful to dispose of any such scrap film except in container provided for such purpose. 3100.813. Concession Stands: It shall be unlawful to maintain any concession stand in or beneath any reviewing stand; provided, however, that nothing in this section shall be deemed to prohibit such concession stands in which soft drinks, confections, tobacco, are sold or dispensed in the event that heat is not used in such stands for the preparation or dispensing of such merchandise. ORD 014ê79wU ×Pì!6b 3100.814. Heating Appliances: No heating appliance shall be maintained in any place of public assemblage tha combustion chamber of which is not adequately guarded to pre- vent contact of any material with the flame. Flame in any such heating appliance shall be so regulated, or guards shall be so arranged, as to prevent injury to person. Such appliances shall be permanently connected with solid pipe or tubing, and no flexible tubing or hose shall be permitted; and when located where likely to be accident- ally moved or overturned shall be securely fastened to the floor or wall. 3100.815. Flammable Decorations: The use of highly flammable scenery, drapes, or decorations is prohibited in all places of public assemblage; provided, however, that the County Fire Warden may permit the use of such scenery, drapes or decorations when the same are treated with a fire resistive solution. 3100.816. Flammable Liquids: Regulations for the storage of flammable liquids or combustible material in liq- uid form are in Part 6 of this Code. Part 9 MOTION PICTURE PROJECTION 3100.901. Protection Machine: No projection machine shall be maintained in any building or structure for the pur- pose of projecting motion pictures unless such projection machine is maintained in a motion picture projection booth constructed in accordance with the provisions of the County Building Ordinance. It shall be unlawful for any person own- ing, controlling, or managing any place of public assemblage to use or permit to be used any motion picture projection equipment which is damaged or worn to such an extent as to create a fire hazard. 3100.902. Installation: Every projection machine, ex- cept portable type, shall be kept securely fastened to the floor to prevent overturning. 3100.903. Motion Picture Film Storage: No nitro- cellulose motion picture film shall be stored in any building or structure in which is located any projection machine unless such film is stored in a motion picture proj-ect.ion booth, or as otherwise provided in Part 16. Provided, however, that nothing in this section shall be deemed to prohibit the storage of film in any film laboratory in connection with any projec- tion booth. 3100.904. Protection Booth: 1 Doors: Projection booth doors shall be maintained in a completely closed position at all times by means of an adequate spring or other device when such doors are not being actually used for the purpose of ORD 014ê79wU ×Pì!7bpermitting ingress and egress to or from such enclosure, booth or room. Such door shall open outwardly and shall not be equipped with any latch. 2. Combustibles=Furniture: Each booth shall at all times be kept clean and free and clear from any flammable or combustible material of any kind other than such motion picture film, cement, or other material necessary to be used during any exhibition or show in progress at any given time. No shelving, furniture, or fixture shall be maintained or used within any such booth unless such shelving, furniture or fixture is constructed or composed of non-combustible material. 3. Film: No motion picture film except such film as is being run or is being transferred to or from any such projection machine, or is being repaired or rewound, shall be kept or maintained in any such booth unless such film is kept or maintained in a metal box or cabinet constructed of galvanized iron or steel with metal partitions or shelves, and shall have tight self-closing doors of iron or steel. No solder shall be used in the construction of such metal boxes or cabinets. No motion picture film shall be kept, stored nor main- tained in any such booth except such film as is being used or to be used in the current show or exhibition at any given time and such additional film as may be necessary to sub- stitute during any program, show or exhibition in case of an emergency, provided, however, that no more than twenty 20) reels of film shall be stored in any such booth, It shall be unlawful for any person owning, controlling or managing any place of public assemblage or any projection- ist to use or permit to be used any motion picture film which is in such a damaged condition, or in which the sprocket holes are torn or damaged to such an extent as to creaie a fire haz- ard. 4. Shutters: Regulations for shutters are in the County Building Ordinance. 5. Smokine: No person shall smoke or permit any per- son to smoke in any such booth, or in any sanitary toilet room or electrical generator room in connection therewith. 3100.905. Permit and License to Operate Projection Machine: No person shall operate, or cause to permit the operation of any projection machine, unless such person so operating possesses a valid permit issued by the County Fire Warden. Provided, however, that any person operating a pro- jection machine in only a public or private institution, Div- isions 1 and 3 as classified in Part 10 of this Code, shall not be required to obtain such permit, nor shall Sections 3100.908, 3100.907, 3100.908, 3100.909 or 3100.910 apply to such operator, but in lieu thereof any such person so oper- ating shall obtain a special permit issued by the County Fire Warden by successfully passing an examination conducted by said Fire Warden. Provided, further, that the County Fire Warden may issue a temporary permit to a projectionist who has filed an application for examination and who has exhibited ORD 014ê79wU ×Pì!8bevidence that he is possessed of sufficient knowledge to operate a projection machine. Such temporary permit shall be good only until the date of the next examination, and no such temporary permit shall be issued to an applicant who has failed the examination. 3100.906. Application: Application for permit to operate projection machine shall be filed with the County Fire Warden, at which time applicant shall pay to said County Fire Warden the sum of Ten Dollars to pay a portion of the cost of investigation and examination. Such application shall be accompanied by photograph in triplicate of the ap- plicant. The likeness and size of such photograph shall be approved by the County Fire Warden, but in no case shall it be of a size less than one and one-quarter JJ) inches square. Such sum so paid shall be deposited to the credit of the General Fund. Applications shall not be accepted by the County Fire Warden from persons less than eighteen 18) years of age, nor from any projectionist whose license has been re- voked, until a period of twelve 12) months has elapsed sub- sequent to the date of such revocation. The County Fire Warden shall notify each applicant of the date and time of such examination at which he should ap- pear. Any applicant who does not so appear shall be failed in such examination. 3100.907. Examining Board: Applicants shall be ex- amined by an examining board of three 3) projectionists pos- sessing valid County permits; two 2) to be selected by the County Fire Warden and the third by said two. In no event, however, shall more than two(2) members of such board retain active membership in any labor organization. Appointment to such board shall be made for a period of one 1) calendar year, subject to earlier removal by the County Fire Warden. In the event of any vacancy, member to fill such vacancy shall be selected by the remaining members of board. Each member of such board shall be paid Ten Dollars $10.00) for each examination participated in by him. It shall be the duty of the County Fire Warden to ap- point one or more substitute examiners, who shall fill any temporary vacancy caused by the absence of any of the regular examiners, and such appointment shall carry with it the respon- sibilities and compensation as set forth for the regular exam- iners. 3100.908. Examination: Examinations shall be held at such intervals as the County Fire Warden shall deem necessary for the examination of such applicants. In no event, however, shall an examination be held more often than every thirty 30) days nor unless there shall have been filed not less than six 6) applications. If it shall be found, after due and thorough examination by the board, that said applicant is possessed of sufficient knowledge, skill and ability to operate a projection machine with proficiency and safety, the County Fire Warden shall thereupon issue for such applicant a projectionist=s ORD 014ê79wU ×Pì!9bpermit stating that upon examination it has been found that the permittee therein named is possessed of sufficient knowl- edge, skill and ability to operate projection machines with proficiency and safety, which shall permit such applicant to operate projection machines in the City of Baldwin Park. Any appeal by any applicant for review of examination rating must be made in writing within five 5) days from the date on which notice of rating is mailed by the County Fire Warden. 3100.909. Permits: Such permit shall have a photo- graph of the permittee securely affixed thereto. Each person to whom such a permit is issued shall keep his permit herein- above provided for conspicuously posted on,or near the door of the booth, enclosure or room in which is located the pro- jection machine operated by such person, and such permit shall not be transferable nor used by any person other than the per- son for whom same is issued, 3100.910, Renewal of Permits: 1) Projectionist per- mit shall be issued for a twelve 12) months period, and shall not be valid for more than twelve 12) months after the date of issuance. Such permit shall be renewed not later than thirty 30) days after the date of expiration, upon the pay- ment to the County Fire Warden of the sum of Two Dollars and Fifty Cents, when accompanied by one 1) photograph of the size specified in Section 3100,906, Renewal of such permit after the above period shall require a renewal fee of Five Dollars. 2) All fees collected by the County Fire Warden shall be deposited to the credit of the General Fund. 3) No permit shall be renewed unless such permittee has either passed the necessary examination within six 6) months preceding date of application, or such permittee is the holder of a valid permit and has been employed as a pro- jectionist within such preceding six 6) months. No such per- mit shall be issued to any such applicant or permittee not having been so examined or having been so employed until an examination, as previously set forth, has been satisfactorily passed. 4) The County Fire Warden shall not renew any permit if application for such renewal is not filed within one 1) year after the expiration of the last permit or renewal granted. Such last permit thereby becomes null and void, 5) If the holder of any valid permit, prior to the expiration of such permit, enlists in, or is inducted into any branch of the Federal armed service, such permit remains valid until one 1) year after the discharge of such person there- from, 3100,911. Revocation of Proiectionistts Permit: Viola- tion of any provision of this Code relative to maintenance or operation of projection machine or booth, use or storage of film, incompetency in the operation or maintenance of projec- tion machine or booth, shall be cause for the revocation of ORD 014ê79wU ×Pì!:bsaid projectionist's permit by the County Fire Warden. Such revocation shall not take place, however, until a hearing relative to such revocation is held by the examining board. 1. Cause for Immediate Suspension: Operation of any projection machine by any projectionist while under the in- fluence of liquor, morphine, or other habit-forming drug shall be cause for immediate suspension of such projection- istts permit by the County Fire Warden. No such projection- ist shall continue the operation of any such projection ma- chine, nor shall any person, firm, corporation, or associa- tion of persons permit any such projectionist to operate any such projection machine pending a hearing relative to perma- nent revocation by the examining board. 2. Notice: Notice shall be given in writing to any such projectionist not less than forty-eight 48) hours prior to the date of such hearing; which notice shall state the ground of complaint, and shall also state the time when and the place where such hearing will be held. Such projection- ist may produce at such hearing any evidence or reason why such permit should not be suspended or permanently revoked. 3. Hearing: The examining Board shall without com- pensation conduct a hearing of charges against any projec- tionist, together with any evidence submitted by any such projectionist in defense. Such Board shall submit its find- ings, together with recommended action to be taken, to the County Fire Warden. 4. Action: Upon receipt of such report from the Ex- amining Board, the County Fire Warden shall take such action as he deems necessary and proper, whether such action be repri- mand, restoration, or temporary or permanent revocation of such permit. Part 10 HEALTH, HOUSING AND EDUCATIONAL INSTITUTIONS For the purpose of this Part, institutions shall be classified as follows: Division 1. Hospitals, sanitariums, rest homes, homes for the aged, asylums, orphanages, children's institutions, children's homes, nurseries, and similar institutions. Division 2. Hotels, Apartment Houses. Division 3. Public parochial or private schools. 3100.1001. Housing: 1. No person shall be housed above the ground floor in any Division 1 institutional building with a capacity of six 6) or less when such building is of Type V construction, as defined by the County Building Ordinance. Buildings housing more than six 6) persons shall meet the re- quirements of the County Building Ordinance for such occu- pancy. Provided, however, that this section shall not apply to the housing of employees, members of the management, or their families; nor prohibit the housing of three 3) or less aged persons on the second floor of such building; nor apply to the housing of able-bodied persons not more than forty-five BIB] 39007-U01 ORD-U02 014-U02 LI2-U03 FO94595-U03 FO94601-U03 DO94693-U03 C5-U03 ORDINANCES-U03 10/16/2006-U04 ROBIN-U04